If  two  or  more  separable  connectors  are 
provided,  they  shall  be  configured  or 
arranged so that the other and vice-versa 
will  not  accept  the  mating  connector  for 
one,  if  it  will  result  in  an  improper 
connection. 

 

Connectors  between  modules  must  be 
inserted until they click. 

 

Do  not  put  too  much  stress  on 
connectors  in  order  to  avoid  detachment 
of connectors. 

 

Please  contact  your  Panasonic  Authorized 
Representative  with  questions  regarding 
other electrical connections if needed.  

 
Junction Box and Terminals 

 

Modules  equipped  with  one  junction  box 
contain  terminals  for  both  positive  and 
negative polarity, and bypass diodes. 

 

One terminal is dedicated to each polarity 
(with  the  polarity  symbols  engraved  onto 
the  body  of  the  junction  box)  (see 
Figure 3). 

 

Conduit 

 

For  applications  where  wire  conduits  are 
used,  follow  the  applicable  codes  for 
outdoor  installation  of  wires  in  conduits. 
Minimum  diameter  of  wire  conduit  is  4 
mm

2

 

Verify that all fittings are properly installed 
to  protect  wires  against  damage  and 
prevent moisture intrusion.  

 

DIODES 
Bypass Diodes 

 

When  the  modules  in  series  strings  are 
shaded  partially,  it  may  cause  reverse 
voltage across cells or modules, because 
the current from other cells in the same 
series  is  forced  to  flow  through  the 
shaded area. This may cause undesirable 
heating to occur.  

 

The  use  of  a  diode  to  bypass  the 
shaded  area  can  minimize  both  heating 
and array current reduction. 

 

All  modules  are  equipped  with  factory 
installed  bypass  diodes.  The  factory 
installed  diodes  provide  proper  circuit 
protection  for  the  systems  within  the 
specified system voltage, so that you do 
not  need  any  other  additional  bypass 
diodes.  

 

Specifications  of  bypass  diode  for 
VBHNxxxSJ25  series  are  as  follows; 
Number  of  bypass  diode:  3  diodes, 
Number of series cells per bypass diode: 
24 cells / diode. Specifications of bypass 
diode  for  VBHNxxxSJ40  series  are  as 
follows;  Number  of  bypass  diode:  4 
diodes, Number of series cells per bypass 
diode: 22 cells / diode (See Figure 4). 

 

Contact  your

 

Panasonic  Authorized 

Representative for proper diode type, if it 

is  necessary  to  add  or  change  diodes 
due to system specifications. 

 

MAINTENANCE 

 

Some  maintenance  is  recommended  to 
maintain optimal output performance of the 
modules.  

 

It  is  also  recommended  to  inspect  the 
electrical  and  mechanical  connections 
annually. 

 

If  you  need  electrical  or  mechanical 
inspection  or

 

maintenance,  it  is 

recommended  to  have  a  licensed 
authorized  professional  carry  out  the 
inspection  or  maintenance  to  avoid  the 
hazards of electric shock or injury. 

 

The  return  of  any  modules  will  not  be 
accepted by Panasonic unless prior written 
authorization has been given by

 

Panasonic. 

 

As  part  of  our  policy  of  continuous 
improvement  Panasonic  reserves  the  right 
to  change  product  specifications  at  any 
time without prior notice.  
 

Anti-reflection Glass surface cleaning 
Cleaning of dirt

 

 

If  the  module  surface  becomes  dirty,  it 
may reduce output power. 

 

 It is recommended to clean the surface 
of the module with water and a soft cloth 
or sponge. 

 

 To  remove  persistent  dirt,  the  module 
can  be  washed  with  a  micro-fiber  cloth 
and ethanol. 

 

Never  use  abrasive  detergent,  strong 
alkaline  detergent  and  strong  acid 
detergent to clean any part of the module. 
Performance  of  solar  panel  may  be 
reduced.  Please  be  very  careful  since 
warranty  will  not  cover  the  damage  from 
detergent. 

 

When  cleaning  with  detergent,  it  is 
recommended  to  start  with  smallest  area 
and  from  the  edge  of  solar  panel  in 
order to check no damage occurs to the 
glass. 

 

It  is  recommended  to  read  carefully  the 
manuals  of  detergent  and  understand 
notes on usage and first-aid treatment. 
 

Cleaning of soiling from handling 

 

Unlike  the  persistent  dirt,  soiling  of 
surface  from  holding  the  glass  will  not 
affect  performance  of  solar  panel. 
Therefore  cleaning  is  not  necessary  for 
this  soil  on  glass  surface  caused  by 
handling.  In  case  customer  prefers 
cleaning,  following  is  the  recommendation 
of cleaning methods. 

 

Wipe  gently  with  clean  cloth  and  neutral 
glass  detergent  or  weak  alkaline  glass 
detergent. 

 

After that, clean surface of glass with wet 
and clean cloth. 

 

Acid and strong alkaline detergent and the 
detergent  which  forms  protective  layer  on 
the surface of the glass must be avoided. 
Those detergents may damage surface of 
the  glass  and  affect  on  the  performance 
of  solar  panel.  Please  be  very  careful 
since warranty will not cover the damage 
from detergent. 

 

When  cleaning  with  detergent,  it  is 
recommended  to  start  with  smallest  area 
and  from  the  edge  of  solar  panel  in 
order to check no damage occurs to the 
glass. 

 

It  is  recommended  to  read  carefully  the 
manuals  of  detergent  and  understand 
notes on usage and first-aid treatment. 

 

Disclaimer of Liability

 

Panasonic  does  not  assume  responsibility  and 
expressly disclaims liability for loss, damage, or 
expense  arising  out  of,  or  in  any  way 
connected  with  installation,  operation,  use,  or 
maintenance by using this manual.   
Panasonic  assumes  no  responsibility  for  any 
infringement of patents or other rights of third 
parties, which may result from use of modules.  
No  license  is  granted  by  implication  or  under 
any patent or patent rights. The information in 

Figure 4: Number of series cells per 

bypass diode 

24 cells / diode 

 

24 cells / diode

 

 

24 cells / diode

 

 

22 cells / diode

 

 

 

22 cells / diode

 

 

 

22 cells / diode

 

 

 

22 cells / diode

 

VBHNxxxSJ25 series

 

VBHNxxxSJ40 series

 

 

Summary of Contents for Photovoltaic Module HIT VBHN245SJ25

Page 1: ...40 Contents Please read before installation Safety Precautions General Information 2 Warning 2 Cautions 2 General Safety 2 Installation General 2 Notes on Installation 3 Operating Conditions 3 Special Conditions 3 Specifications Notes on Specifications 3 Application Class of Product 3 Fire class of Product 3 Mechanical Loading 3 Certifications 3 Wiring General 3 Module Wiring 3 Array Wiring 3 Eart...

Page 2: ...ks may occur do not install the module where flammable gases or vapors are present Never leave a module unsupported or unsecured Do not drop a module Do not use or install broken modules to avoid the hazard of fire electric shock and injury Do not artificially concentrate sunlight on a module to avoid the hazard of fire or damage Do not touch the junction box terminals to avoid the hazard of elect...

Page 3: ... to meet the requirements for safety class II Fire class of product HIT R fill the fire class C that provides to IEC61730 2 Class C roof coverings are effective against light fire test exposures Under such exposures roof coverings of this class afford a light degree of fire protection to the roof deck do not slip from position and are not expected to produce flying brands Mechanical Loading The mo...

Page 4: ...t be accepted by Panasonic unless prior written authorization has been given by Panasonic As part of our policy of continuous improvement Panasonic reserves the right to change product specifications at any time without prior notice Anti reflection Glass surface cleaning Cleaning of dirt If the module surface becomes dirty it may reduce output power It is recommended to clean the surface of the mo...

Page 5: ...ith general household waste For proper treatment recovery and recycling of old products please take them to applicable collection points in accordance with your national legislation For more information about collection and recycling please contact your local municipality Penalties may be applicable for incorrect disposal of this waste in accordance with national legislation Customer Services For ...

Page 6: ... protection rating A 15 15 Factory Installed Bypass Diodes 3 3 Silicon hetero junction Monocrystalline silicon amorphous silicon hetero junciton Mechanical Specifications Model VBHN245SJ25 VBHN240SJ25 Length mm 1580 1580 Width mm 798 798 Height mm 35 35 Weight kg 15 15 Electrical Specifications Figure 1 1 Dimensions Dimensions Module type VBHNxxxSJ25 with connector and cable Dimension in mm Backsi...

Page 7: ...1 Installation A Solar Module Metal clamp B 2 places Metal clamp A 2 places Mounting Structure Rail 1 48 38mm 1 48 38mm 1 37 35mm 0 43 11mm Dimension in mm Optional Mounting Range A Figure 1 2 Optional Mounting Range A Note Fixing span must not exceed 1040mm Dimension in mm Optional Mounting Range B Figure 1 3 Optional Mounting Range B Note Fixing span must not exceed 1040mm Cable Figure 3 Configu...

Page 8: ...lled Bypass Diodes 4 Silicon hetero junciton Monocrysttaline silicon amorphous silicon hetero junction Mechanical Specifications Model VBHN285SJ40 Length mm 1463 Width mm 1053 Height mm 46 Weight kg 18 Electrical Specifications Figure 5 Dimensions Dimensions Module type VBHNxxxSJ40 with connector and cable Dimension in mm Backside Side Note A module is installed using 4 points symmetrical mounting...

Page 9: ...ler Module Mounting Structure Rail M8 Bolt Spring washer M8 Nut Flat washer Figure 6 2 Installation B Flat washer Spring washer Installation reference Figure 6 1 Installation A Solar Module Metal clamp B 2 places Metal clamp A 2 places Mounting Structure Rail 1 48 38mm 1 48 38mm 1 81 46mm 1 34 34mm ...

Reviews: