42
AHU Kit – Installation Instructions – 09/2021
Product description
3
Technical data and limitations – PACi systems –
R32
AHU Kit
PAW-280PAH2(L/M) or PAW-280PAH3M
Outdoor unit – PACi Standard
U-60PZ2E5
U-71PZ2E5 U-100PZ2E5 U-125PZ2E5 U-140PZ2E5 U-100PZ2E8 U-125PZ2E8 U-140PZ2E8
Nominal cooling capacity
kW
6.0
7.1
10.0
12.5
14.0
10.0
12.5
14.0
Nominal heating capacity
kW
6.0
7.1
10.0
12.5
14.0
10.0
12.5
14.0
Piping connections
Liquid pipe
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas pipe
Inch (mm)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Piping length
Min / Max
m
3 / 40
3 / 40
5 / 50
5 / 50
5 / 50
5 / 50
5 / 50
5 / 50
Precharged length (
R32
)
Max
m
30
30
30
30
30
30
30
30
Additional refrigerant charge (
R32
) due to extended piping
length
g/m
35
35
45
45
45
45
45
45
Ambient temperature
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
Heating (Min / Max) °C WB
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
AHU unit under “standard conditions”
Air volume flow
Cooling (Min / Max) m³/h
780 / 1,320
780 / 1,320
900 / 2,160 1,140 / 2,280 1,200 / 2,400 900 / 2,160 1,140 / 2,280 1,200 / 2,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
1.3 / 1.4
1.3 / 1.4
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
Heat exchanger face area
Min / Max
m
2
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
AHU unit under “special conditions A
2
”
Air volume flow,
subject to restrictions
2
Cooling (Min / Max) m³/h
780 / 1,450
780 / 1,600
900 / 2,300 1,140 / 2,500 1,200 / 2,600 900 / 2,300 1,140 / 2,500 1,200 / 2,600
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
1.3 / 1.8
1.3 / 2.0
1.5 / 2.6
1.5 / 2.6
1.5 / 2.8
1.5 / 2.6
1.5 / 2.6
1.5 / 2.8
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
kg/dm
3
0.83
0.83
0.83
0.83
0.83
0.83
0.83
0.83
Max. additional refrigerant charge (
R32
)
kg
0.33
0.50
0.58
0.58
0.74
0.58
0.58
0.74
Max. pipe length
m
30
25
35
35
35
35
35
35
Max. ambient temp. for pump down
°C
n/a
n/a
35
25
35
35
25
35
See footnotes overleaf.
AHU Kit
PAW-280PAH2(L/M) or PAW-280PAH3M
Outdoor unit – PACi Elite
U-36PZH2E5 U-50PZH2E5 U-60PZH2E5 U-71PZH2E5 U-100PZH2E5 U-125PZH2E5 U-140PZH2E5
Nominal cooling capacity
kW
3.6
5.0
6.0
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
4.0
5.6
7.0
8.0
11.2
14.0
16.0
Piping connections
Liquid pipe
Inch (mm)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas pipe
Inch (mm)
1/2 (12,7)
1/2 (12,7)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Piping length
Min / Max
m
3 / 40
3 / 40
3 / 40
5 / 50
5 / 85
5 / 85
5 / 85
Precharged length (
R32
)
Max
m
30
30
30
30
30
30
30
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
g/m
20
20
35
45
45
45
45
Ambient temperature
Cooling (Min / Max) °C DB
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
Heating (Min / Max) °C WB
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
AHU unit under “standard conditions”
Air volume flow
Cooling (Min / Max) m³/h
360 / 870
510 / 990
780 / 1,320
780 / 1,320
900 / 2,160 1,140 / 2,280 1,200 / 2,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
– / 1.3
– / 1.3
– / 1.4
– / 1.8
1.7 / 2.1
1.7 / 2.1
1.7 / 2.1
Heat exchanger face area
Min / Max
m
2
– / –
– / –
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
AHU unit under “special conditions A
2
”
Air volume flow,
subject to restrictions
2
Cooling (Min / Max) m³/h
360 / 870
510 / 1,080
780 / 1,600
780 / 1,700
900 / 2,400 1,140 / 2,600 1,200 / 2,700
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
– / 1.5
– / 1.5
– / 1.9
– / 2.2
1.7 / 3.0
1.7 / 3.0
1.7 / 3.0
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
kg/dm
3
0.83
0.83
0.83
0.83
0.83
0.83
0.83
Max. additional refrigerant charge (
R32
)
kg
0.17
0.17
0.41
0.33
0,74
0,74
0,74
Max. pipe length
m
30
30
30
40
65
65
65
Max. ambient temp. for pump down
°C
n/a
n/a
n/a
35
43
43
43
Continued on the following page. See footnotes overleaf.
27.07.2021, JW
Please add PAW-280PAH3M also here
02.08.2021, cH
Rows adjusted and PAH3M added.
06.08.2021, JW: OK