Service Valve Operation Method
1. Location of service valves and access ports
2. Method of operating service valves
The service valves fall into two categories types as follows.
Notes: 1.
Copper packing, Cap and Nut must be installed after the work. (Gas leak prevention)
2. Check Gland nut loosening of the service valves, and fasten them if any looseness
exists.
3. Fastening torques are as follows.
Cap:
30
5 N
・
m,
Nut:
13
1 N
・
m,
Gland Nut:
10
1 N
・
m
3. Relationship between each seat position and refrigerant flow direction
A
Back seated position
(Counterclockwise
turn limit)
C
Front seated
positon
(Clockwise turn
limit)
B
Mid-position
(Stem height approx. 15 mm)
Access port of low pressure
service valve
Access port of high pressure
service valve
Detail of access ports location
Packing
Nut
Stem
Copper packing
Cap
Gland nut
Access port
Copper
packing
Cap
Packing
Nut
Access port
Stem
Gland nut
High pressure and low pressure
service valve
Oil service valve
A
: Back seated position
(Turn the stem fully counter-
clockwise)
Access port is
Access port is
Open
.
Closed
.
B
: Mid-position
(Stem height approx. 15mm)
・
High pressure side
Approx. 3 and
a
half turns
・
Low pressure side
Approx. 3 turns
All three service valve openings
are accessible.
C
: Front seated position
(Turn the stem fully clockwise)
Access port is
Access port is
Closed
.
Open
.
Location of service valves
Front of refrigeration unit
4