Application Functions
6-8
6.3.3 Sequence at main power OFF
The operation sequence at the main power supply OFF is changed with combination, such as 6007h/6807h
(Abort connection option code), Pr5.07 (main power off sequence), and PSM Pr.02 (main power off detection
time).
Basically, the deceleration function defined by CoE (CiA402) is valid until the deceleration function defined by
servo (MINAS-A6) side is activated by detecting the main power supply OFF (between L1, L2, and L3) of the
power supply module.
-
When "No action" is set by 6007h/6807h = 0, the CoE (CiA402) deceleration function does not operate,
and the deceleration function on the servo (MINAS A6) side operates.
-
When the main power DC-bus voltage decreases, Err13.0 (Main power undervoltage protection [PN])
occurs with the highest priority, causing the operation in accordance with Pr5.10 (Sequence at alarm).
This section explains deceleration function on the servo (MINAS A6) side.
Please refer to "TECHNICAL REFERENCE EtherCAT Communication Specification (SX-DSV03456)"
for details of deceleration function on the CoE (CiA402) side.
Relevant parameters
Relevant parameters
Class No. Attribute Title
Range
Unit
Function
5
07
B
Sequence at main
power OFF
0 to 9
-
Specify the status during deceleration after main power interrupt or
after stoppage.
5
08
B
L/V trip selection
upon main power
off
0 to 3
-
Select LV trip or servo OFF upon occurrence of main AC power
alarm.
Setup the condition to detect main AC power OFF alarm when the
main AC power is kept interrupted for a time longer than the time
set by PSM Pr.02.
bit0: 0: The servo off according to the setting of 6007h/6807h
(Abort connection option code) or Pr5.07.
1: Trip with Err 13.1 Main power undervoltage protection.
(Note 1 )
bit1: 0: Detect main AC power OFF alarm only when servo is in
ON state.
1: Always detect main AC power OFF alarm.
5
09
C
S
Detection time of
main power off
20 to
2000
(Note 2)
ms
Set up main AC power alarm detection time.
Main AC power OFF detection is disabled when the setting value is
2000.
5
11
B
Torque setup for
emergency stop
0 to 500
%
Set up the torque limit at emergency stop.
When setup value is 0, the torque limit for normal operation is
applied.
6
36
R
Dynamic brake
operation input
setup
0 to 1
-
Sets between enabling and disabling dynamic brake (DB) operation
input by I/O.
This function is available only when the main power is turned off.
0:Disabled
1:Enabled
PSM
Pr.
Name
Setting
range
Shipping
setting
Unit
Content
02
Main power off
detection time
0 to 2000
70
ms
Sets up the main power off detection time.
Main power off is not detected if the setting value is set smaller than
20 or is set to 2000. (Note 1)
(Note 1) To use this setting with a smaller value than the shipment value, please check matching with your power supply environment.
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...