Sensory Probes are located under this labelled
panel.
PAGE 26
CAUTION:
Refer to relevant State or
Territory legislation relating to safe
working heights
CAUTION:
Personnel access atop the
cabinet is limited to 100kg personnel
and only when the cabinet is empty
of product/merchandise. Do not walk
atop cabinets, sedentary work/access
only is permitted. Always have suitable
PPE and working from heights SWMS
in place. Work as far from edges as
feasible. If unsafe, do not access the
top of the cabinet
NOTE:
Replace racks and shelves etc,
as necessary to store requirements.
Incorrect pan and display tag
configurations may compromise case
performance.
Ensure case earthed when proceeding
with electical components. Electric
shock or fire may occur if not correctly
processed.
To install the probe:
1. Unscrew the plate from the ceiling panel to get
access to the conduit for the probe wire. A coloured
piece of wire acting as a draw string is located
behind the plate in the conduit
2. Secure the end of the sensor wire to the draw string
wire.
3. On the roof of the case, pull draw wire and sensor
wire all the way through the conduit.
4. Seal end of the conduit with putty or silicon
5. Repeat for each case
3.11 INSTALLING SENSOR PROBES
FIGURE 3AD
3.12 MOUNTING FIXTURES
INSTALLATION
SMED SEMI VERTICAL - HUSSMANN
NOTE:
The sensor orientation
should be as per the control system’s
recommendations. Some control
system’s sensors require air to be in
same direction as sensor, others at 90°
The discharge air control sensor
should be located in the air stream
only and should not make contact with
any metal parts. .