background image

7

BASIC OPERATION

For details on the procedures for operating the product, refer “

our web site (http://

panasonic.net/id/pidsx/global)

”.

 

The modes and shortcut functions that can be used from the home screen after 

the power is turned ON are as follows.

1.

 Display switching mode (long press UP key for 2 seconds)

You can change the display of the digital display / SUB (green) as needed for the task.

Normal measured value

Label

Calculated value

HIGH set value

LOW set value

Sensor head measured value

2.

 Teaching mode (long press LEFT key for 2 seconds)

Automatically set HIGH and LOW set values and output HI / GO / LO decision values.

<Example> 1-point teaching

Measured value (press ENTER key when master workpiece is present)

+0.1000 shift

-0.1000 shift

HIGH set value

LOW set value

*When tolerance = 0.1000 (default state)

3.

 HIGH set value fine adjustment function (short-press UP key)

You can fine adjust the HIGH set value as needed.

4.

 LOW set value fine adjustment function (short-press DOWN key)

You can fine adjust the LOW set value as needed.

5.

 Bank mode (long press DOWN key for 2 seconds)

You can write / read the HIGH set value or LOW set value to / from a specified bank (1 to 3).

Bank 1

Bank 3

Bank 2

6.

 Setting mode (long press RIGHT key for 2 seconds)

You can change basic settings or configure advanced function settings.

Basic settings

Bank settings

Advanced settings

Calibration settings

Copy settings

Maintenance

Calculation settings

Initialization

7.

 Preset (short-press PRESET key)

You can perform zero-point adjustment, and shift  to any preset value.

You can cancel preset by long-pressing the preset key for 2 seconds.

8.

 Key lock (long press ENTER key + EXIT key for 3 seconds)

You can prevent accidental key operation during measurement.

Key lock setting

Key lock release

Key lock activated

8

CAUTIONS

 

For the controller DC power supply, only use a power supply that is isolated by 

means of an isolation transformer or otherwise.

 

Risk of short-circuiting and damage to the controller or power supply if a trans-

former such as an auto transformer is used. Risk of short-circuiting and damage 

to the controller or power supply if incorrectly mounted or connected.

 

 The controller 

HG-SC

□ is designed to be used with the special sensor head 

HG-S

□.

 

If used with other than the special sensor head option, the specifications will not 

be met and product malfunctioning or damage may occur.

 

This product has been developed / produced for industrial use only.

 

 This product uses an EEPROM. The EEPROM has a service life of one million setting operations.

 

●  Do not use this product outside the range of the specifications. Risk of an accident 

and product damage. There is also a risk of a noticeable reduction of service life.

 

● Verify that the supply voltage fluctuations are within the rating.

 

If power is supplied from a commercial switching regulator, ensure that the frame 

ground (F.G.) terminal of the power supply is connected to an actual ground.

 

Do not use during the initial transient time after the power supply is switched ON.

 

 Make sure that the power supply is OFF while performing wiring or connecting a slave unit work.

 

 Take care that short-circuit of the load or wrong wiring may burn or damage the product.

 

 After you have completed wiring work, check the wiring carefully before switching 

on the power.

 

Do not wire in parallel with a high-voltage line or power line, or run through the 

same conduit. Risk malfunctioning due to induction.

 

 Do not apply stress such as excessive bending or pulling to the extracted part of a cable.

 

This product is suitable for indoor use only.

 

Avoid dust, dirt, and steam.

 

 Do not use this sensor in places where it may come in contact with corrosive gas, etc.

 

 Ensure that the product does not come into contact with organic solvents such as thinner.

 

Ensure that the product does not come into contact with strong acid or alkaline.

 

Ensure that the product does not come into contact with oil or grease.

 

 

This product cannot be used in an environment containing flammable or explosive gases.

 

● Performance may not be satisfactory in a strong electromagnetic field.

 

●  This product is a precision device. Do not drop or otherwise subject to shock. Risk 

of product damage.

 

Never attempt to disassemble, repair, or modify the product.

 

 When the product becomes unusable or unneeded, dispose of the product appro-

priately as industrial waste.

9

SPECIFICATIONS

Type

Master unit

Slave unit

High performance type

Standard type

Wire-saving type

Model No.

NPN output

HG-SC101

HG-SC111

HG-SC112

HG-SC113

PNP output

HG-SC101-P

HG-SC111-P

HG-SC112-P

Number of connectable units

Up to 15 slave units can be connected per master unit.

(When communication unit consolidated: up to 14 slave units)

Supply voltage

24V DC ±10%, including 0.5V ripple (P-P) 

Current consumption (Note 2)

70mA or less (when sensor head is connected)

Analog current output 

(Note 3)

• 

Current output range: 4 to 20mA / F.S.

(default value)

• 

Error output: 0mA

• 

Linearity: ±0.25% F.S.

• Load impedance: 250Ω MAX.

Control output

(Output 1 / Output 2 / Output 3)

<NPN output type>

NPN open-collector transistor

• 

 Maximum sink current: 50mA (Note 4)

• 

 Applied voltage: 30V DC or less

(between output and 0V)

• 

 Residual voltage: 1.5V or less

(at 50mA sink current)

• 

 Leakage current: 0.1mA or less

<PNP output type>

PNP open-collector transistor

• 

 Maximum source current: 50mA (Note 4)

• 

 Applied voltage: 30V DC or less

(between output and +V)

• 

 Residual voltage: 1.5V or less

(at 50mA source current)

• 

 Leakage current: 0.1mA or less

Short-circuit protection

Incorporated (automatic reset type)

Decision output

NO/NC switching type

Alarm output

Open when alarm

External input

(Input 1 / Input 2 / Input 3)

<NPN output type>

Non-contact input or 

NPN open-collector transistor

• 

Input condition

Invalid: +8V to +V DC or open

Valid: 0 to +1.2V DC

•   Input impedance: Approx. 10kΩ

<PNP output type>

Non-contact input or 

PNP open-collector transistor

• 

Input condition

Invalid: 0 to +0.6V DC or open

Valid: +4V to +V DC

•   Input impedance: Approx. 10kΩ

Trigger input

Input time 2ms or more (ON)

Preset input

Input time 20ms or more (ON)

Reset input

Input time 20ms or more (ON)

Bank input A / B

Input time 20ms or more (ON)

Response time

3ms, 5ms, 10ms, 100ms, 500ms, 1,000ms switching type

Display resolution

0.1μm

Display range

-199.9999 to 199.9999mm

Protection

IP40 (IEC)

Contamination level

2

Ambient temperature

-10 to +50°C (No dew condensation or icing allowed) (Note 4), Storage: -20 to +60°C

Ambient humidity

35 to 85% RH, Storage: 35 to 85% RH

Elevation

2,000m or less (Note 5)

Material

Case: Polycarbonate, Cover: Polycarbonate, Switches: Polyacetal

Cable

0.2mm

2

 2-core (brown, blue 

lead wires) / 0.15mm

2

 7-core 

composite cable, 2m long

0.15mm

2

 7-core 

composite cable, 

2m long

0.15mm

2

 6-core 

cabtyre cable, 2m 

long

Weight (controller only)

Approx. 140g

Approx. 140g

Approx. 130g

Approx. 60g

Notes: 1) Measured at a supply voltage of +24V DC and an ambient temperature of +20°C, unless otherwise indicated.

 

2) Current consumption does not include analog current output.

 

3) Linearity F.S. = 16mA, and is linearity with respect to digitally measured values. Response time is the time 

follwing measured value update.

 

4) When slave units are connected to the master unit, the maximum sink current / source current of the control 

output and ambient temperature vary depending on the number of connected slave units as shown below.

Number of connected slave units

Maximum sink current / source 

current of control output 

Ambient temperature

When communica-

tion unit consolidated

1 to 7 units

1 to 6 units

20mA

-10 to +45°C

8 to 15 units

7 to 14 units

10mA

 

5) Do not use or store in an environment pressurized to atmospheric pressure or higher at an altitude of 0m.

10

ERROR DISPLAY

Error Display

Description

Action

Both NPN output types and PNP output types 

are connected.

Connect only units of the same output type.

Number of connectable units exceeded.

Connect no more than 15 slave units per master unit.

(When communication unit consolidated: up to 14 

slave units)

Cannot communicate between controllers.

Switch OFF the power, make sure the controllers are 

connected correctly, and then switch ON the power 

again.

The calculation function is valid but no slave 

units are connected.

Change calculation mode to OFF.

The calculation function is valid but an insuffi

-

cient number of slave units are connected.

Change calculation mode to OFF, or change the cal-

culation application selection setting.

The saved number of connected units does not 

match the actual number of connected units.

Set the number of connected units check function to 

OFF.

• 

Sensor head not connected.

• 

 Broken wire in sensor head connection cable.

• 

Sensor head failure.

• 

 Check if the sensor head is correctly connected.

• 

Check if there is a broken wire in the sensor head 

connection cable. If there is a broken wire in the 

sensor head connection cable, replace the cable.

• 

Replace the sensor head.

The thrust on the sensor head stroke is above 

the specified range.

Check the sensor head mounting and measurement 

object installation position, and adjust so that the 

stroke is within the specified range.

Unable to preset by external input.

Check if the power just been switched on or reset has 

just been input, or if a display value is outside the dis

-

play upper/lower limit or an alarm has occurred.

• 

Failed to write to or read from EEPROM.

• 

The EEPROM write count is over the ser-

vice life of 1 million.

• 

Switch the power OFF then ON, and execute ini-

tialization of the controller from setting mode.

• 

If the controller does not recover after the above, it 

is possible that the EEPROM write count is over  

1 million. Replace the controller.

The detection output load has short-circuited 

and excessive current is flowing.

Switch OFF the power and check the load.

An error has occurred in the internal controller. Switch the power OFF then ON, and execute initial-

ization of the controller from setting mode.

http://panasonic.net/id/pidsx/global

Overseas Sales Division (Head Office) 

2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan 

Phone:  +81-568-33-7861  FAX:  +81-568-33-8591

For sales network, please visit our website.

PRINTED IN JAPAN

© Panasonic Industrial Devices SUNX Co., Ltd. 2016

Reviews: