background image

5

Notes

1.  The maximum incident light intensity displayed depends on the selected response 

time.

 

Response time

Incident light intensity

STD, H-SP, FAST

Max. 4,000

LONG

Max. 8,000

U-LG, HYPR

Max. 9,999

2.  When the timer is used, set the timer time.

 

Timer range

Timer period

Display

1/10ms

Approx. 0.1 – 999.9ms

1 – 9999

3.  When setting the shift amount using the digit display, the setting range differs 

depending on the response time, as shown in the table below

 

Response time

Shift amount

STD, H-SP, FAST

Max. 4,000

LONG

Max. 8,000

U-LG, HYPR

Max. 9,999

4. 

T

o clear the value, turn off the time period holding function. Turning off the power 

switch also clears the value.

5.  If you have selected limit teaching for the changed incident light intensity (Algo-

rithm setting = 

), note that the shift direction of the threshold differs depending 

on the combination of the sensing output status and the sensing output operation.

 

Sensing output 

status

Sensing output 

operation

Shift direction

ON

Light-ON

ON

Dark-ON

+

OFF

Light-ON

+

OFF

Dark-ON

Details on the menu items

Pro1 menu

Menu item

Default 

setting

Description

Response time 

setting

Set response time.

Timer setting

Set operation and delay of the timer.

Timer range 

setting

Set the timer range and the timer time (display 

example with OFF-delay timer) 

Shift amount 

setting

Set the shift amount for the threshold value when 

you execute limit teaching (see “Limit teaching” on 

page 3).

Pro2 menu

Menu item

Default 

setting

Description

Teaching lock 

setting

Be able to prevent from wrong operation of teaching.

The lock is deactivated, teaching can be 

performed.
The lock is activated, teaching is not possible.

Setting items 

in the digital 

display

Select what should be displayed in red on the digital 

display. Choose between the incident light intensity 

displayed as a percentage or the peak/bottom value.

Peak/bottom 

hold function 

setting

Peak/bottom values are refreshed regularly.
Peak/bottom values are held.

Setting of digital 

display turning

When you set this parameter to ON, the digital dis-

play will be rotated by 180°.

ECO setting

The power consumption can be lowered.

Power consumption is normal.
If no key is pressed for 20s in RUN mode, the 

digital display turns OFF.
If no key is pressed for 20s in RUN mode or 

the key lock function has been activated, the 

digital display and all indicators turn OFF.

Pro3 menu

Menu item

Default 

setting

Description

Display 

adjustment 

setting

Set the incident light intensity to the target value. When 

you set the display adjustment while the incident light 

intensity does not have enough margin, the display 

shows a blinking 

.

Display adjustment OFF
Set the display to 0. This redefines the initially 

displayed value as zero. 

Reset setting

If you select the setting 

, the amplifier returns to the 

factory settings.

Interference 

prevention 

setting

The interference prevention function is disabled.

Use up to 4 different emitting frequencies. A 

maximum of 4 sensor heads can be cascaded 

per frequency setting.
Set this to minimize the effect of ambient 

environment.

When this setting is set, mutual interference 

prevention function is disabled.

The response time is as follows when 

 or 

 is 

selected

Response 

time

F-1: max. 0.8ms, F-2: max. 0,9ms

F-3: max. 1.0ms, F-4: max. 1.7ms

(Not affected by “

 ”

 set

-

ting.

(

Response time setting

)

STD: max.500

μ

s, LONG: max. 

4ms, U-LG: max. 8ms,HYPR: 

max. 48ms 

(

selectable

)

Threshold 

value follow-

up cycle

The incident light intensity can be monitored for the 

cycle (1 to 9,999s) specified, for example when varia-

tions in incident light intensity are expected. When the 

threshold value follow-up cycle is set, the threshold 

value is adjusted according to the shift based on the 

incident light intensity detected. However, the threshold 

value is not stored

Sensing 

output 

setting

Select whether the threshold value should be followed 

when the output is OFF or when the output is ON.

Storage 

cycle set-

ting

Select the cycle for storing threshold values in the non-

volatile memory. The valid range is 1 to 250 times

Algorithm 

setting

When limit teaching is used, the threshold value 

is modified by the shift amount. The direction 

of the threshold shift differs depending on the 

combination of the sensing output status and 

the sensing output operation, see note

(Recommended when using thru-beam-type 

fiber or specular reflective-type fiber)
When auto teaching is used, the threshold value 

is followed up on the basis of each cycle. (Rec-

ommended when using reflective-type fiber)

Notes

The direction of the threshold shift differs depending on the combination of 

the sensing output status and the sensing output operation.

 

Sensing output 

status

Sensing output 

operation

Shift direction

ON

Light-ON

ON

Dark-ON

+

OFF

Light-ON

+

OFF

Dark-ON

13

Error codes and troubleshooting

The following error codes may appear in the digital display

Error 

code

Description

Remedy

The non-volatile memory is broken or 

reached the end of its working life.

Please contact our office.

Error writing on the non-volatile memory

Load of the sensing output is short-cir-

cuited causing an over-current to flow.

Check that all amplifiers are 

firmly attached and that there 

is no gap between amplifiers.

Summary of Contents for FX-550L Series

Page 1: ...itivity setting mode 9 Mode indicator L D Light ON Dark ON mode yellow Lights when setting Sensing output operation mode 3 Mounting Installation to a DIN rail 1 Attach the railing on the rear of the ampli fier to the DIN rail 2 Push the amplifier in the direction of the arrow as illustrated so that it attaches securely 1 2 Removal from a DIN rail 1 Push the amplifier forward 2 Lift the front part ...

Page 2: ...161 Preventive maintenance threshold value detection lag time setting Index162 Operating time Index163 Number of data save opera tions Index164 Notification Flag Setting Index168 Notification Event Code Index169 Note For the IO Link communication setting refer to the attached sheet Index list 6 Operation procedure If you change settings press the SET key before you turn the power OFF Otherwise you...

Page 3: ...ng the shift amount refer to PRO1 in section 12 PRO MODE 2 At the time of limit teaching UP key System command Index2 0x4B DOWN key System command Index2 0x4C Auto teaching When the sensing object is moving use this teaching method 1 Press and hold the SET key for a long time 2 Run the sensing object on the production line and hold down the SET key system command Index2 0x47 3 The display shows in...

Page 4: ... key select Press the SET key MODE key select cancel Press the UP or DOWN key Device moves automati cally to the next item MODE indicator PRO yellow Procedure SET SET SET SET PRO1 250μs 2ms 4ms 24ms SET SET SET SET SET SET PRO2 SET PRO3 SET SET SET SET SET SET SET PRO1 OFF SET SET SET OFF ON OFF Display adjustment setting Turning OFF Turning ON Eco setting Full Setting of digital display turning I...

Page 5: ...ou set the display adjustment while the incident light intensity does not have enough margin the display shows a blinking Display adjustment OFF Set the display to 0 This redefines the initially displayed value as zero Reset setting If you select the setting the amplifier returns to the factory settings Interference prevention setting The interference prevention function is disabled Use up to 4 di...

Page 6: ...y voltage 12 to 24V DC 10 15 ripple P P10 max Power con sumption Normal operation 960mW max current consumption 40mA max at 24V supply voltage Eco mode 720mW max current consumption 30mA max at 24V supply voltage IO Link commu nication C Q 1 IO Link specification Ver1 1 Baud rate COM3 230 4kbit s Process data length PD 4byte Control output DO 2 PNP open collector transistor Maximum source current ...