13
START-UP PROCEDURE
Connect the power then turn on the main switch on ERV.
If the ERV does not run, please check the wiring.
Fill in beginning time on the OA filter before
starting up the unit.
Using a manometer, measure the differential pressure of fresh air and exhaust air
respectively, then adjust the dampers for balancing airflows to make the test value
reach the differential pressure of setting volume as shown below.
<Control panel>
EA knob:
Set the exhaust air volume with this knob.
The factory default is 100 CFM.
ASHRAE time knob:
The operation state will be changed with this knob. It is in units of
1 hour, for example: set to “10”, 10 minutes (ON) 50 minutes (OFF) 10 minutes (ON)...
cycle operation. The factory default is 60 Min/H.
Main switch:
Power on or off for ERV. Push the main switch
completely to the on/off position when turning on/off.
1
2
3
4
SA knob:
Set the supply air volume with this knob.
The factory default is 100 CFM.
The unit will consume some electricity unless you turn off the main switch.
OPERATION
Note
The SA air volume is limited less than “EA air 20 CFM” when the outdoor
temperature is -22 °F (-30 °C)~14 °F (-10 °C). For example, when the EA air volume
setting is 50 CFM and the SA air volume setting is 100 CFM, actually the EA air volume
will be 50 CFM and the SA air volume will be 70 CFM.
Note
Low
Low
High
High
Fresh
Supply
air (SA)
The relation between volume
and differential pressure (reference)
The numbers in this table are the values after
installation.
Outside
air (OA)
Exhaust
air (EA)
Return
air (RA)
Differential pressure (Pa)
Stale
Volume
(CFM)
Fresh
50
60
70
80
90
100
35
35
45
45
50
50
65
65
80
80
90
90
55
70
75
90
95
115
120
145
155
195
175
225
Stale
OA filter
BEGINNING TIME:
FV-10VEC2
FV-10VEC2H
FV-10VE2
FV-10VE2H
FV-10VEC2
FV-10VEC2H
FV-10VE2
FV-10VE2H
2
3
4
Check static pressure.
Install the plug covers back when the check is complete.
1