Conversion Characteristics
FP0 RTD Unit
10
4.3 Ni1000
Input range: -30.0°C to 150.0°C/-22.0°F to 302.0°F), resolution: 0.1K/0.1°F
-300
1500
8191
-30.0
150.0
(°C)
Input v alue
C
o
n
v
e
rt
e
d
v
a
lu
e
-220
3020
8191
-22.0
302.0
(°F)
Input v alue
C
o
n
v
e
rt
e
d
v
a
lu
e
A/D conversion table
Analog input
value (°C)
Digital output
value
Analog input
value (°F)
Digital output
value
-30.0
-300
-22.0
-220
+150.0
+1500
+302.0
+3020
Processing if the input value range is exceeded
Analog input
value (°C)
Digital output
value
Analog input
value (°F)
Digital output
value
-30.1 or less
8191
-22.1 or less
8191
+150.1 or more
+302.1 or more
RTD broken
RTD broken