Technical/Programming Manual
FT1020G3 Rev 2.2.1
142
21
System properties (settings)
21.1
System properties dialog box
To open System properties dialog box as shown in Figure 46, go to the EBLWin menu
System | Properties…
Figure 46 EBLWin "System properties" dialog box, Page 1 and 2
Opens via the "System" pop-up menu or via menu "System" (Properties...).
21.1.1
Name
Normally the installation name (Max. 22 characters).
21.1.2
User definable text
Two rows of 40 characters are available for user definable text messages. The text will be
shown in all Control Units. For more information see FT1020G3 Operation Manual.
21.1.3
System properties, Page 1
21.1.3.1
Alert Annunciation
See also chapter "17.12", page 114.
Acknowledgement time:
30 sec.
Default set at 30 seconds, allowable between 0-120 seconds is possible to set.
Investigation time:
3 minutes.
Default set at 3 minutes, allowable between 1-9 minutes.
Number of zones:
1
Default set to 1 zone, allowable between 1-4 zones.
Multiple alarms allowed within same zone
Normally only one Alert Annunciation Alarm is allowed within the zone. If more Alert
Annunciation alarms within the zone are allowed, this checkbox should be marked.
149
149
Alarm from two or more alarm points within the same zone will activate normal fire alarm, i.e. the "Fire brigade TX" output w ill
be activated.