FT1020G3 Rev 2.10.4
9
Disable / Re-enable Alarm Devices
Outputs programmed for sounders or OWS
i.e. type "Alarm devices", can be
collectively
disabled for all control units during Fire alarm or Alert Annunciation alarm, this is done via
menu H2/B4. The disablement is indicated by LED
Fault / Disablements
"
General
disablements
" (L10) and "
Alarm devices
" (L11), which are steady ON.
In case of a fire, the sounders or OWS will
remain
disabled, i.e. the alarm devices will not
sound until they are re-enabled again via menu H2/B4.
Note:
Outputs of type "Alarm devices" cannot be individually disabled, not even via menu
H2/B2 “Disable or Re-enable Output”.
See also chapter "Test of alarm devices” (H8/S4), page 155. All outputs of type "Alarm
devices" for a specified or all Control Units, can be activated for an alarm device test.
24
Including Addressable siren 4487, Addressable sounder base 3379, Addressable light indicator 4383, Wireless
smoke detector 4611, and all Visual Alarm Devices 448X.