156
Operation Manual
FT1020G3 Rev 2.10.4
29.5
Safe Shut Down of Control Unit (H8/S5)
It's not recommended
to power down a Control Unit (i.e. no 230 V
AC
and no battery)
without first performing a safe shut down of the Control Unit. Safe shut down will save the
SSW in a Flash ROM and put the CPUs at rest.
If no safe shutdown is performed, it may also generate a fault when you power up the
control unit again:
FAULT
: Read/write site data (SSW), control unit xx"
It's highly recommended
to perform a safe shut down after commissioning the installation
and calibrating the supervised outputs, changing passwords etc. in order to save the new
valid values and codes.
Safe shut down can be performed from any Control Unit and any Control Unit can be
selected. A Control Unit without a front has to be shut down from another Control Unit.
Note:
By restart and power down, the Fault TX output(s) will be "activated".
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H8.
H8 Maintenance
"
↲
"
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
Scroll to menu S5.
S5 Safe shut down of control unit
"
↲
"
Shut down control unit
0
0?
No
Yes
Write control unit
number and press "▼"
to select "Yes".
"▼"
"
↲
"
Ready for shut-down, break the power.
Automatic restart within xxx seconds!
xxx
will start at 300 seconds and countdown to 000 before
the control unit will restart automatically. During the
countdown the buzzer will start sounding since the
communication between the Main and MMI boards has
stopped. (Can be silenced via push button "Silence buzzer".)
The SSW is now saved
and the Main board and
MMI board CPUs are at
rest. You can now
power down the control
unit.
If not, the control unit
will restart automatically
after 300 seconds (5
minutes).
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...