115
Operation Manual
FT1020G3 Rev 2.10.4
23.2
Output (H2/B2)
All programmable outputs in the FDCIE and outputs in units connected to the COM loops
(
except outputs of type "Alarm device"
) can be individually disabled.
If you try to disable an output of type "Alarm device" it will be treated as if it does not exist,
see below.
Disabled output:
Even if its control expression (trigger condition) is fulfilled (true), the
output will not be activated.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H2.
H2 Disable or re-enable
"
↲
"
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
Scroll to menu B2.
B2 Output
Via menu B2, a loop unit
output, C.U. output S0-
S3 / R0-R1 and exp.
board 4581 output can
be disabled.
"
↲
"
Disable output
Loop unit
0
00000 output 0
Use the soft key
"Change type of
disablements" to toggle
between:
Loop unit output
Control unit output S
Control unit output R
Exp. board output
Write loop unit technical
number and output
number and press "
↲
" to
disable, which will be
indicated with "
√
" and a
beep. The output will be
automatically shown in
the Re-enable list
Change type of
disablements
Write loop unit technical
number and output
number,
(e.g. 000001 and 0).
"
↲
"
Disable output
Loop unit
0
00000 output 0
√
-- Re-enable list (1) ---------------------------------------------
Loop unit 000001 output 0
If the specified output
does not exist, it will be
indicated with "X"
instead of "
√
" and a
beep.
Use the soft key "
|
" to
toggle between
Disable
and
Re-enable
list
.
Change type of
disablements
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...