All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00012 2000-05-15 

2006-08-31 

 

Type numbers 

6275 

Heat detector, fixed temperature 60

°

C, latching 

6276 

Heat detector, fixed temperature 80

°

C, latching 

 

 

 

Technical data 

Voltage (V DC) 

  rated 
  allowed 
  normal 

 

24 
12-30 
24 

Current consumption at nom. volt. 
(mA) 

  quiescent (detector only) 
  active (detector only) 

Depending on the type of base it is plugged into.  For more details, see 
the base respectively. 


Max. 70  (Current limitation in all EBL equipment) 

Ambient temperature (

°

C) 

  operating 
  storage 

6275 / 6276 

-10 to +40 / -10 to +60 
-25 to +70 / -25 to +70 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating (estimated) 

IP22 

Alarm temp. (fixed temp.) 

60

°

C (6275),  80

°

C (6276) 

Weight, detector only (g) 

70  

Colour 

grey  (N8, Munsell colour code) 

Approvals 

CE, EN54-5, response grade 1 (6275) 

CE, EN54-8, temp. range 1 detector (6276) 

 