EBL128 Planning Instructions V2.0.x
73
10.2
Logic
The logic is set in the EBLWin dialog box "Voltage or Relay Output".
(•) Normally open / low
Normally open relay contacts / normally
low voltage output.
( ) Normally closed / high
Normally closed relay contacts / normally
high voltage output (24V DC).
10.3
Supervised
A voltage output is normally supervised (default). By un-marking this
checkbox the voltage output will be not supervised.
NOTE!
A normally high output is not supervised.
See also chapter "Programmable voltage outputs (S0-S1)", page 20.
10.4
Output signal period
Each output uses an "Output signal period", which controls the
output's activation. The following are available:
Steady (continuous)
Intermittent 0.8s/0.8s
User defined 1
User defined 2
User defined 3
User defined 4
User defined 5
User defined 6
User defined 7
User defined 8
User defined 1-8 can be built up with type and time.
The following types are available:
Steady (continuous)
Intermittent
One pulse
Steady Delayed Activation
Intermittent Delayed Activation
One pulse Delayed Activation
Steady Delayed De-Activation
The following times are available:
Delay time (when required)
Pulse length time (when required)
Pulse off time (when required)
De-activation time (when required)
See also chapter "Output Signal Periods", page 146.