Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
20
4.1.3
Short-circuit on the COM loop
Short-circuit between the
L
(SA) and
C
(SB) wires
7
will generate a
fault with the following fault message:
FAULT: Short-circuit SCI
nn
<-> SCI
nn
nn
= A, B, 00, 01, 02, 03 and up to 63 depending on if none, one or
several isolators are used. A & B are the built-in control unit
isolators in the A- and B-direction respectively.
If no isolator is used the information will be:
A
<->
B
.
If one isolator (no. 0) is used:
A
<->
00
or
00
<->
B
If two isolators (no. 00 and no. 01) are used:
A
<->
00
,
00
<->
01
or
01
<->
B
...and so on.
The short-circuit is in the specified segment, e.g.
A
<->
0
.
In case of short-circuit in more than one segment on the COM loop,
the fault messages will be similar to the message shown for several
breaks (cut-offs),
FAULT: Several...
(see above).
Each 10
th
minute a new attempt is made to communicate in the A-
direction only.
When the fault is corrected (no short-circuit) the communication
automatically returns to communicate in the A-direction only.
6
4.2
Programmable voltage outputs (S0-S1)
The outputs S0-S1 are normally supervised (monitored).
8
One to five
33K resistors can be connected
9
. Connections to "J1:5-8" according to
drawing 128-22. When the connections are finished, a calibration has
to be performed
. See also the EBL128 Operating Instructions chapter
"Calibration of supervised outputs (menu H5/A1)".
Each output has to be programmed (via EBLWin) regarding:
Type (Control, Fire ventilation, Alarm device, etc.)
Output signal period (steady, intermittent, pulse, delay, etc.)
Supervised / Not supervised
Logic, i.e. normally low (default)
or
normally high (24 V DC)
10
.
Control expression (containing one or more trigger conditions)
NOTE!
The outputs S0-S1 are as default programmed as outputs for
alarm devices.
7
Depending on the cable type / length and where the loop short-circuit is
located, it can take up to 10 seconds before the fault is generated.
8
A normally high output can not be supervised. The supervision voltage is
1.5 – 3.6 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to activated output.
9
P.c.b. no. 9285-
5A
: One to five 470 nF capacitors. The calibrated value
has to be in the range 4K7 – 50K and 1 to 5 x 470 nF respectively.
10
Regarding
system voltage
, see chapter "Technical data", page 143.