EBL128 Planning Instructions V2.0.x
161
COM loop units (input units, etc.)
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
Analog smoke detector 2300 / 2304 + analog base 2312
141
1.7 / 1.8
3.7 / 3.8
Analog smoke detector 3304 + analog base 3312
142
0.3
2.3
Analog heat detector 3308 + analog base 3312xx
142
0.3
2.3
Analog heat detector, enclosed 3309
142
0.2
1.7
Analog multi detector 4300 + analog base 3312xx
142
0.3
2.3
Analog smoke detector 4301 + analog base 3312xx
142
0.3
2.3
Analog multi detector 4400 + analog base 3312xx
0.3
143
1.3
144
Analog smoke detector 4401 + analog base 3312xx
Addressable heat detector 2340 / 2341
141
2
5
Addressable zone interface, isolated 2226
145
3
6
Addressable IS zone interface 2821
145
3
6
Isolated zone interface 2822
3
6
Addressable zone interface 2335
5
20
Addressable manual call point 2333
2
5
Addressable manual call point 3333 / 3339
2
5
Addressable manual call point with isolator 4433 / 4439
1.6
2.7
Alarm Acknowledge Facility Control (AAFC)
146
2
5
Addressable detector base 2330 + detector
Incl. external line.
1.7
3.5
3.9
147
13.2
NOTE!
On each COM loop, up to 5 sensors / detectors can have their LEDs lit at the same time.
141
External indicator (LED) current consumption. 2216: add 2 mA. 2217 /
2218: add 1 mA.
142
External indicator (LED) current consumption. 2216: add 2 mA. 2217 /
2218: add 1 mA.
Analog base with isolator 4313 can be used instead of Analog base 3312.
143
Plus 0.025 mA if green polling LED is used.
144
Plus 0.5 mA if External indicator (LED) is used (e.g. 2218).
145
2226 / 2821 also require external power supply, 24V DC, 30 mA.
146
This unit is available on the Australian market only.
147
Ext. LED current consumption max. 1 mA. Alarm state on detector and
external line: 15.4 mA.
NOTE!
The external line can be used for an ext.
indicator (LED) or for conventional detector(s) that will get the same
presentation number (zone-address) as the detector plugged in the base.