background image

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00503 2006-04-04 2 

2007-01-29 

 

Type numbers 

4550 

EBL128 c.i.e. (128 addresses).  Batteries are not included. 

4552 

RS485 transceiver component, for up to four display units, i.e. Ext. Fire Brigade 
Panels 1826 / 1828, Ext. Presentation Unit 1728 and/or Alert Annunciation Units 
1735 / 1736. 

4551 

Expansion board holder.  (For two 4580 and two 4581 expansion boards.) 

4580 

8 zones expansion board.  (Max. two per c.i.e.) 

4581 

8 relays expansion board.  (Max. two per c.i.e.) 

The 4580 board can be used to connect 

conventional

 detectors and manual call points to 

EBL128.  An end-of-line capacitor (470 nF) shall be connected in the last alarm point on each 
zone line. 

More information is available in the EBL128 Planning Instructions & Operating Instructions. 

 

Technical data 

Voltage 
  primary  (V AC) 
  secondary  (V DC) 
    normal 
    by battery backup 

 
230 
 
24 
21 - 30 

Current consumption (mA) 

Depending on connected units, etc. See EBL128 Planning Instructions. 

Ambient temperature (

°

C) 

  Operating 
  storage 

 
-5 to +40 
-40 to +75 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating (estimated) 

IP32 

Inputs 

1 COM loop for 128 addresses 

 

1 programmable input  (NO / NC).   R>200

 = open circuit.  Max. 2 mA 

Outputs 

1 programmable supervised voltage output (24 V DC, max. 500 mA)  

 

1 programmable supervised voltage output (24 V DC, max. 200 mA)  

 1 

programmable 

relay output. 

3

  Default set for routing equipment (Fire 

brigade tx).   

 

1 non-programmable relay output. 

3

  For routing equipment (Fault tx). 

 

Power supply (24 V DC, max. 200 mA) for routing equipment  

2

 

 

Power supply (24 V DC, max. 500 mA) for external equipment (Web-
server, up to 4 ext. FBPs, etc.)    Web-server requires approx. 65 mA.  

1

 

Interfaces 

RS232 ("D" connector) for a PC (Win128) 

 

RS232 for a Web-server 1588 

 

Socket for an optional RS485 transceiver, for ext. FBPs, EPUs and/or 
AAUs. 

Size H x W x D (mm) 

511 x 416 x 123 

Weight (kg) 

12.2   (Excl. Batteries) 

Colour (metal cabinet) 

Aluminium & light grey (NCS S1500-N, PMS Cool Grey 2)  

Approvals 

CE

;  

EN54 parts 2 & 4

.  The front is fully 

SS3654

 compliant. 

Note!  

All voltages are nominal.  For more information see EBL128 Planning Instructions MEW00508. 

1

  Continuous 500 mA, 620 mA during 30 ms. 

2

  Continuous 200 mA, 240 mA during 110 ms. 

3

  Relay contacts:  max. 1 A @ 30 V DC.

 