background image

INSTRUCTION MANUAL

Separate type · digital sensor controller

DPC-L100

 Sereis

For liquid / gas

MJE-DPCL100 No. 0081-79V

Thank you very much for purchasing Panasonic products. 

Read this Instruction Manual carefully and thoroughly for the correct and optimum 

use of this product.

Kindly keep this manual in a convenient place for quick reference.

WARNING

 

Never use this product as a  device for personnel protection.

 

In case of using devices for personnel protection, use products which 

meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel 

protection applicable in each region or country.

 

The product for use inside Japan complies with Japanese Measurement 

Laws. Avoid using the product model for outside of Japan within Japan.

1

PART DESCRIPTION

Notes: 1)  Attach the unit switch plate corresponds to the set pressure unit.

 

2)  The product for use inside Japan can be set only to “MPa” or “kPa.”

2

MOUNTING

 

The sensor mounting bracket  

MS-DP1-6

 is available as an option. 

When mounting the sensor onto the 

sensor mounting bracket, etc., the tight-

ening torque should be 0.5N·m or less.

 

T h e   p a n e l   m o u n t i n g   b r a c k e t  

MS-DP1-2

 (optional), as well as the 

front cover 

MS-DP1-3

 (optional) are 

also available.

 

For mounting of the panel mounting 

bracket, refer to the Instruction Manual 

enclosed with 

MS-DP1-2

.

3

CONNECTION OF PRESSURE SENSOR HEAD

 

In case of initial set up or reset, select pressure range.

 

incase changing pressure sensor head, check pressure range.

Connection method

1.

 

Insert the pressure sensor head cable into the 

product’s connector area for the pressure sen-

sor head as shown in the right figure.

Disconnection method

1.

  Pressing the release lever of the pressure sen-

sor head cable, pull out the connector.

Note: Do not pull by holding the cable without pressing the re-

lease lever, as this can cause cable break or connector 

break.

<Terminal pin arrangement>

Terminal pin No.

Terminal name

1

Sensor head supply voltage

2

Analogue input

3

0V

4

Not used

4

WIRING

Connection method

1.

 

Insert cable with connector 

CN-66A-C□

 into 

the product’s connector area for a power / I-O 

cable as shown in the right figure.

Disconnection method

1.

  Pressing the release lever of the cable with con-

nector, pull out the connector.

Note: Do not pull by holding the cable without pressing the release 

lever, as this can cause cable break or connector break.

<Terminal pin arrangement>

Terminal pin 

No.

Terminal name

Terminal pin 

No.

Terminal name

1

+V

4

Comparative output 1

2

Analogue voltage 

/ current output

5

Comparative output 2

3

0V

6

External input

Connector area for a 

power supply / I-O cable

Connector area for a 

pressure sensor head

Output 1 operation 

indicator 
Lights up when com-

parative output 1 is ON
Output 2 operation 

indicator 
Lights up when com-

parative output 2 is ON
Mode selection key

Set value UP key

Set value 

DOWN key

Attach area for 

unit switch plate

(Note 1, 2)
Main display

Sub display

Release lever

Pressure 

sensor 

head cable

<Connector area of the pressure sensor head cable>

e-con: 1473562-4

[Tyco Electronics AMP G.K.]

Release lever 

Cable with 

connector 

CN-66A-C

<Connector area of the cable with connector>

Housing: PAP-06V-S

[JST Mfg. Co., Ltd.]

M3 (length 6mm) 

screws with washers

Accessory with

 

MS-DP1-6

Sensor mounting bracket 

MS-DP1-6

 (Optional)

1 2 3 4 5 6

1 2 3 4

9

MENU SETTING MODE

 

The mode will change to RUN mode when the mode selection key is held 

down during this setting process. In doing so, changed items before holding 

down the mode selection key have been set.

Note:  1)  In case connecting pressure range 1MPa type of pressure sensor head to Japanese model controller, 

only “MPa” or “kPa” can be set. Also, in case connecting 3.5MPa or more type, setting item for unit 

change is not displayed.

 

2)  in case of connecting pressure range 3.5MPa type of sensor head to out side of japan type controller.  

“ 

 ” is not displayed.

Setting Item

Factory setting

Description

Comparative 

output 1 output 

mode setting

Sets comparative output 1 output mode.

Comparative 

output 2 output 

mode setting

Sets comparative output 2 output mode.

N.O. / N.C. 

selection

Sets when Nomal Open (N.O.) or Normal Close (N.C.).

Initial state of excepting OFF of the comparative output 2 setting is “ 

 .”

Analogue voltage 

/ current output 

selection

Selects Analogue voltage output or analogue current output.

Function setting

Sets Auto-reference function or remote zero-adjustment function and current 

value hold function or peak / bottom 2 function.

Response time 

setting

Sets response time.

The response time can be select from 5ms, 10ms, 25ms, 50ms, 100ms, 

250ms, 500ms, 1,000ms or 5,000ms.

Display color 

selection of the 

main display

Selects display coler of main display.

Unit selection

Selects pressure unit.

RUN mode

EASY mode

Hysteresis

mode

Press for 2 sec.

Window com-

parator mode

<Comparative output 2 output mode setting>

EASY mode

Hysteresis

mode

Window

comparator 

mode

OFF mode

<N.O. / N.C. selection> (When the comparative output 2 output mode setting is set to OFF)

N.C.

N.O.

<N.O. / N.C. selection> (When the comparative output 2 output mode setting is set to other than OFF)

Output 1: N.O.

Output 2: N.O.

Output 1: N.C.

Output 2: N.C.

Output 1: N.O.

Output 2: N.C.

Output 1: N.C.

Output 2: N.O.

<Analogue voltage / current output selection>

Analogue 

voltage 

output mode

Analogue 

current out-

put mode

<Function setting>

OFF

Auto-reference 

function mode

Remote zero-

adjustment 

function mode

Current 

value hold 

function

Auto-peak / 

bottom hold 

2 function

<Response time setting>

10ms

5ms

5,000ms

<Display color selection of the main display>

Red when ON

Green when OFF

Green when ON

Red when OFF

Always red

Always green

<Unit selection> (Note 1)

kPa (Note 2)

MPa

bar

kgf/cm

2

psi

<RUN mode>

<Comparative output 1 output mode setting>

10

PRO MODE

 

The mode will change to RUN mode when the mode selection key is held 

down during this setting process. However, changed items before holding 

down the mode selection key have been set. 

Setting item

Factory setting

Description

Sub display 

selection

Changes the indication of the sub display in RUN mode.

“ 

 ” :  Displays nothing. 

“ 

 ” :  Current pressure unit is displayed. 

“ 

 ” :  Desired No. can be shown. 

“ 

 ” :  Desired numbers, alphabets (some of them cannot be displayed) 

and signs can be shown.

Display speed 

selection

Changes the speed of the displayed pressure value on the main display.

Hysteresis fixed 

value selection

Sets hysteresis of the EASY mode and the window comparator mode.  

(8 steps)

Displayed color 

relation selection

The setting contents set at the displayed color setting in Menu setting mode 

can be related with either comparative output 1 or comparative output 2.

External input 

relation selection

The setting contents set at auto reference function and remote zero-adjustment 

function can be shifted to correspond to  either comparative output 1, 2 or 1 / 2.

Eco mode

setting

Current consumption can be lowered. 

“ 

 ” :  Normal operation  (ECO mode is OFF.)

“ 

 ” :  If any key operation is not carried out for approx. 5 sec. in RUN 

mode, the display becomes dark. 

“ 

 ” :  If any key operation is not carried out for approx. 5 sec. in RUN 

mode, the display is turned OFF.

Press any key to temporarily show the normal indication.

Setting check 

code

Current setting contents can be checked. For codes. refer to “Code table.”

Setting copy 

mode

The setting of the master side sensor can be copied to the slave side sensors. 

For details, refer to “ 

SETTING COPY FUNCTION

.”

“ 

 ” :  The setting contents are copied.

“ 

 ” :  The setting contents are copied, and the slave side sensor goes 

into key-lock state.

Reset setting

Returns to default settings (factory settings).

By pressing dowun mode key when “   ” mode, becomes default settings 

(factory settings).

RUN mode

<PRO mode>

Hold down 

for 4 seconds

<Sub display selection>

Display OFF

Unit display

No. display

Standard

<Display speed selection>

500ms

250ms

<Hysteresis fixed value selection> (1 level: Approx. 1 digit) (When Pa unit is selected.)

RUN mode

<Sub display selection>

When “ 

 ” is set

When “ 

 ” is set

Change the displayed 

details with

Set pressure 

range is displayed 

on sub display.

Custom display

1,000ms

Min.

Max.

<Displayed color relation selection>

When “No. display” or “Custom display” is set in “Sub display selection.”

<External input relation selection>

<Reset setting>

RUN mode

<Eco mode setting>

OFF

Standard

Max.

<Setting check code>

<Setting copy mode>
Copy sending

OFF

Copy sending

ON

Copy sending

ON-L

Copy ready 

state

Relating with 

comparative

output 1

Relating with 

comparative

output 2

Corresponding 

to comparative

output 1

Corresponding 

to comparative 

output 2

Corresponding 

to comparative 

output 1 / 2

Automatic

Code table

 

Main display (first digit form left)

Code

1st digit

2nd digit

3rd digit

4th digit

Comparative 

output 1 output 

mode

N.O. / N.C. 

selection

Comparative 

output 2 output 

mode

N.O. / N.C. 

selection

Analogue 

output

Threshold 

display

External 

input

EASY

N.O.

OFF

-

Analogue 

voltage 

output

Threshold 

value 1

OFF

N.C.

EASY

N.O.

Threshold 

value 2

AREF

Hysteresis

N.O.

N.C.

Threshold 

value 3

ZERO

N.C.

Hysteresis

N.O.

Threshold 

value 4

HOLD

Window  

comparator

N.O.

N.C.

Analogue 

current 

output

Threshold 

value 1

P.b.-2

N.C.

Window  

comparator

N.O.

Threshold 

value 2

-

-

-

N.C.

Threshold 

value 3

-

-

-

-

-

Threshold 

value 4

-

AREF: Auto-reference function, ZERO: Remote zero-adjust function,

HOLD: Current value hold function P.b.-2: peak / bottom hold 2 function

 

Sub-display (5th digit from left)

Code

5th digit

6th digit

7th digit

8th digit

Displayed color of 

the main display

Displayed color 

relation

Response time

Unit selection

(Note)

Display speed

Eco mode

Red when ON

Comparative 

output 1

-

MPa

250ms

OFF

Comparative 

output 2

-

kPa

std

Green when 

ON

Comparative 

output 1

-

kgf/cm

2

Full

Comparative 

output 2

5ms

bar

500ms

OFF

Always red

Comparative 

output 1

10ms

psi

std

Comparative 

output 2

25ms

-

Full

Always green

Comparative 

output 1

50ms

-

1,000ms

OFF

Comparative 

output 2

100ms

-

std

-

-

250ms

-

Full

-

-

500ms

-

-

-

-

-

1,000ms

-

-

-

-

-

5,000ms

-

-

-

11

SETTING COPY FUNCTION

 

This can copy the settings of the master side sensor to the slave side sensor.

 

Be sure to use the setting copy function between the identical models. This 

function cannot be used between different models.

 

Only one sensor can be connected on slave side with a master side sensor 

for the setting copy function.

 

Do not use the setting copy function other than the following wiring, as pulsed output gener-

ates when turning the power ON after setting the master side sensor to the copy ready state. 

Setting procedure

1.

  Set the setting copy function of the master side sensor to “Copy sending ON

” or “Copy sending ON-L” with the pressure sensor head connected, and then 

press the mode selection key so that the sensor is in copy ready state. For de-

tails, refer to 

<Setting copy mode>

 in “

PRO MODE

.”

2.

 

Turn OFF the master side sensor.

3.

  Remove the pressure sensor head and connect the master side sensor with 

the slave side sensor as shown below.

4.

  Turn ON the master side sensor and the slave side sensor at the same time. (Note)

5.

  Set contents (16-bit coded) are shown in orange on the main display of the 

master side sensor and the copying starts. 

6.

  The same code explained above is shown in green on the main display of the slave 

side sensor, and “

   

” is shown on the sub display (When copying is complete.)

7.

  Turn OFF the power of the master side sensor and the slave side sensor and 

disconnect the wire.

*  If copying the setting to another sensor repeatedly, follow steps 

3

 to 

7

.

Note:  Take care that if the power is not turned on at the same time, the setting contents may not be copied.  

To cancel the setting copy mode of master side sensor

1.

  While the slave side sensor is disconnected, turn on the power of the master side sensor.

2.

  Press the mode selection key for approx. 2 seconds.

12

AUTO-REFERENCE FUNCTION

 

The auto-reference function 

corrects the set value using 

the detected pressure value 

during auto-reference input 

as the reference pressure.

 

Using the detected pressure 

value at auto-reference input 

P(a) as a reference, the set 

value 1’ is automatically cor-

rected to “set value 1 + P(a).”

Settable range and set pressure range after correction

 

The setting pressure range is wider than the rating pressure range so that the 

auto-reference function can be handled.

If the corrected set value exceeds the set pressure range when auto-reference 

input is carried out, the set value will be automatically corrected to within the set 

pressure range. Thus, take care not to exceed the set pressure range.

Before auto-

reference

After auto-

reference

ON
OFF
ON
OFF

Atmospheric pressure

P (a) Set value 1 Set value 1’

Detected pressure value 

at auto-reference input

Pressure

Set value 1’ after auto-reference is:

1’ = 1 + P (a)

Master side sensor

Slave side sensor

(Pink) External input

(Black) Comparative output 1

(Blue) 0V

(Brown) +V

Power 

supply

Color code of cable 

with connector

(Pink) External input

(Black) Comparative output 1

(Blue) 0V

(Brown) +V

5

I/O CIRCUIT DIAGRAMS

NPN output type

PNP output type

Notes: 1)  When the analogue current is output, the output load resistance should be 250Ω max.

 

2)  Take care that when the analogue current is output, 5V or more voltage generates. 

 

3)  When using the analogue voltage output, be careful to the input impedance of the connected device.

 

  Furthermore, note that if the cable is extended, the cable resistance will cause the voltage to drop.

6

OUTPUT MODE AND OUTPUT OPERATION

 

The EASY mode, hysteresis mode or window comparator mode can be se-

lected as the output mode for comparative output 1 and comparative output 

2. Refer to <

Comparative output 1 / 2 output mode setting

> in “

MENU 

SETTING MODE

” for details.

EASY mode

 

ON / OFF of the comparative output is controlled in this mode.

Notes: 1)  Hysteresis can be fixed in 8 steps.

 

  Refer to <

Hysteresis fixed value selection

> in “

PRO MODE

” for setting.

 

2) “   ” is displayed for comparative output 1 and “ 

 ” for comparative output 2 on the sub-display. 

Hysteresis mode

 

The comparative output ON / OFF state can be controlled with randomly set 

hysteresis in this mode.

Notes: 1)  “ 

 ” or “ 

 ” is displayed for comparative output 1 and “ 

 ” or “ 

 ” is displayed for com-

parative output 2 on the sub display.

Window comparator mode

 

In this mode, the ON or OFF state of the comparative output is controlled with 

a pressure in the set range.

Notes: 1)  Hysteresis can be fixed in 8 steps.

 

  Refer to <

Hysteresis fixed value selection

> in “

PRO MODE” for setting.”

 

2) “ 

 ” or “ 

 ” is displayed for comparative output 1 and “ 

 ” or “ 

 ” is displayed  for com-

parative output 2 on the sub display.

 

3)  Set the interval between the Lo side and Hi side to hysteresis fixed value or more.

*1

Non-voltage contact, NPN transistor or 

DC 2-wire output

High (5 to 30V DC or Open): Invalid

Low (0.4V DC or less): valid

or

*2

Non-voltage contact, PNP transistor or 

DC 2-wire output

High (5 to +V DC or Open): valid

Low (0.6V DC or less): Invalid

or

Pressure

P

0

ON

OFF

Comparative 

output

H (Hysteresis)

H: Hysteresis fixed (Note 1)

Pressure

Hi

Lo

ON

OFF

H (Hysteresis)

H: 1 digit or more

When using psi unit model for out-

side of Japan, it is 2 digits or more. 

However, the 50MPa pressure 

range model is 20 digits or more.

Comparative 

output

Hi

Lo

ON

OFF

H: Hysteresis fixed (Note 1)

Pressure

Comparative 

output

H (Hysteresis)

H (Hysteresis)

(Gray) Analogue 

voltage / current 

output (Note 1, 2, 3)

(Brown) +V

(Black) Comparative output 1
(White) Comparative output 2
(Pink) External input
(Blue) 0V

12 to 24V DC

±10%

+
-

Load

Load

(*1)

Main circuit

(Brown) +V
(Pink) External input
(Black) Comparative output 1
(White) Comparative output 2
(Gray) Analogue 

voltage / current 

output (Note 1, 2, 3)
(Blue) 0V

Load

Load

(*2)

Main circuit

12 to 24V DC

±10%

+
-

7

SETTING WHEN TURNING ON THE POWER

 

After turning ON the power, set pressure range of pressure sensor head con-

nected to this product. The set pressure range is memorized and the range is 

displayed every time after tuning on the power. Then, move to RUN mode.

 

In case replacing sensor head or resetting it, set the pressure range again.

8

RUN MODE

Setting the threshold value

 

Refer to 

<Comparative output 1 / 2 output mode setting>

 in “

MENU 

SETTING MODE

” for setting conditions.

 

The Sub display conducts the threshold value. Main display does not changed.

Notes: 1)  If the set pressure range is exceeded, “   ” (exceeds the upper limit) or “ 

 ” (exceeds the lower 

limit) will appear on the sub display. “ 

 ” will also appear if the Hi side threshold value exceeds the 

Lo side threshold value when setting the “hysteresis mode / window comparator mode” threshold value. 

 

2)  Auto-reference value and remote zero-adjustment value are displayed. 

 

  For details, refer to “

AUTO-REFERENCE FUNCTION

” and “

REMOTE ZERO-ADJUSTMENT 

FUNCTION.

 

3)  In the dash line box is not displayed when not setting “ 

 ” or “ 

 ” in external input switch. For the 

setting method, refer to<Function setting> in “

MENU SETTING MODE.

Zero-adjustment function

 

The zero-adjustment function forcibly sets the pressure value to “zero” when 

the pressure port is opened.

Note:  Even if the zero-adjustment is conducted, the analogue voltage / current output is not influenced.

Key lock function

 

The key lock function prevents key operations so that the conditions set in 

each setting mode are not inadvertently changed. 

<Key lock set>

<Key lock released>

Peak / bottom hold function

 

The peak / bottom hold functions display the peak value and bottom value of 

the fluctuating pressure. 

For detail, refer to “

PEAK / BOTTOM HOLD FUNCTION

.”

 

The peak value is displayed on the main display and the bottom value is dis-

played on the sub display.

 

the higher vacuum side indicates the peak value, while the lower vacuum side 

indicates the bottom value.

<Peak / bottom hold set>

<Peak / bottom hold released>

-0.1 to 1MPa

0 to 50MPa

0 to 10MPa

0 to 3.5MPa

0 to 1MPa

Pressure range 

setting

Turning ON the power

Check the set 

pressure range
Resetting the 

pressure range

Confirm the set 

pressure range

RUN mode

The set pressure range is displayed.

Hold down

Automatic

Hold down

Automatic

Hold down

Automatic

Blinks alternately

Hold down

Hold down

Display is changed by pressing down.

Automatic

(Note 2)

Blinks alternately

Press down: increase threshold value to high pressure side.
Press down: decrease threshold value to low pressure side.

Comparative

output 1

EASY mode

(Comparative output 2 is OFF)

Hysteresis mode / Window 

comparator mode

 

· Lo side

Hysteresis mode / Window 

comparator mode

 

· Hi side

EASY mode

Comparative

output 2

Comparative

output 1

Comparative

output 2

Comparative

output 1

Comparative

output 2

(Note 3)

Operation chart

Note:  The set values shift in the same manner during the EASY mode or the window comparator mode.

 

The detected pressure value at auto-reference input becomes “zero” when the 

setting of the analogue voltage / current output selection function is changed 

or the power is turned ON again.

 

The auto-reference input value can be checked when setting the threshold value 

in RUN mode. Refer to “

Threshold value setting

” in “

RUN MODE

” for details.

13

REMOTE ZERO-ADJUSTMENT FUNCTION

 

The remote zero-adjustment function forcibly sets the pressure value to “zero” 

when the external signal is input.

The setting value is not corrected when remote zero-adjustment is input. Make 

sure that the pressure and set value during remote zero-adjustment do not exceed 

the set pressure range.

Operation chart

Notes: 1)  The setting values shift in the same manner during the EASY mode or the window comparator mode.

 

2)  The remote zero-adjustment function is applicable only to the comparative output set at the external 

input relation selection. Unset comparative output operates based on the atmospheric pressure.

 

The remote zero-adjustment value is cleared when the setting of the analogue 

voltage / current output selection is changed or the power is turned ON again, 

and normal operation based on the atmospheric pressure is resumed.

 

● The remote zero-adjustment value can be confirmed when setting the threshold 

value in RUN mode. Refer to the threshold value setting in “

RUN MODE

14

CURRENT VALUE HOLD FUNCTION

 

During turning ON the external input, it display continuously current pressure value.

 

Even if holding the display, it is possible to determine output and to change 

threshold value.

 

In case display is held, actual value is not displayed. be sure that impressed 

pressure not exceed the specified value

.

15

PEAK / BOTTOM HOLD FUNCTION

 

In case setting peak / bottom hold 1 setting, displays peak value and bottom 

value in same time after setting.

 

In case of setting peak / bottom hold 2 setting, displays both peak value and 

bottom value in same time in conjunction with output.

In case power is ON (OFF), hold the display until next output is ON (OFF). the 

set value in conjunction with output.

However, in case of setting window comparator, it operate as peak / bottom hold 1 setting.

 

For setting method, refer to “

Peak / bottom hold function

” in “

RUN MODE

.”

16

CAUTIONS

 

This product has been developed / produced for industrial use only.

 

Make sure that the power supply is OFF while wiring.

 

Take care that if a voltage exceeding the rated range is applied, or if an AC 

power supply is directly connected, the product may get burnt or damaged.

 

Take care that wrong wiring will damage the sensor.

 

Do not run the wires together with high-voltage lines or power lines or put them 

in the same raceway. This can cause malfunction due to induction.

 

If power is supplied from a commercial switching regulator, ensure that the frame 

ground (F.G.) terminal of the power supply is connected to an actual ground.

 

In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicin-

ity of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground.

 

Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.

 

Extension up to total 100m (emitter and receiver each for thru-beam type), or less, 

is possible with 0.3mm

2

, or more of conductor cross-section area cable. However, to 

reduce noise, make the wiring as short as possible. If using this product as complaint 

model with CE Marking / UKCA Marking, the power supply line must be 30m or less.

Brinks alternately

External input ON

During normal operation

(each comparative output set to N.O.)

Output

ON

OFF

Applied pressure (kPa) 0

0

10

10

20

20

30

30

40

40

50

50

60

60

Displayed value (kPa)

1

2

10 20

Set value (kPa)

Output

ON

OFF

Applied pressure (kPa) 0

0

10

10

20

20

30

30

40

40

50

50

60

60

Displayed value (kPa)

P(a)

1

10 20

Set value (kPa)

2

30

During auto-reference input

(each comparative output set to N.O.)

• Detected pressure at auto-reference input: 10kPa

• Output mode: Hysteresis mode

During remote zero-adjustment input

(each comparative output set to N.O.)

• Detected pressure at remote zero-adjustment input: 10kPa

• Output mode: Hysteresis mode

Output

ON

OFF

0

0

10

10

20

20

30

30

40

40

50

50

60

-10

1

10 20

2

During normal operation

(each comparative output set to N.O.)

Output

ON

OFF

0

0

10

10

20

20

30

30

40

40

50

50

60

60

1

2

10 20

Applied pressure (kPa)

Displayed value (kPa)

Set value (kPa)

Applied pressure (kPa)

Displayed value (kPa)

Set value (kPa)

<

Bottom hold 2

>

ON

Bottom

value

OFF

OFF

Start

Current 

value

Set

value

ON

<Peak hold 2>

Set

value

Start

ON OFF ON

ON

OFF

Peak value

Current 

value

OFF

 

Make sure that stress by forcible bend or pulling is not applied directly to the 

sensor cable joint.

 

This sensor is suitable for indoor use only.

 

Avoid dust, dirt, and steam.

 

Take care that the product does not come in contact with water, oil, grease, or 

organic solvents, such as, thinner, etc.

 

Do not operate the keys with pointed or sharp objects.

 

Do not use this sensor in places having excessive vapor, dust, etc., or where it 

may come in contact with corrosive gas, etc.

 

Never disassemble or modify the sensor.

 

This product use EEPROM. The EEPROM has lifetime and cannot set more 

then 1 million times of setting.

17

ERROR INDICATION

 

When error is occurred, use the countermeasure listed blow.

Error

message

Cause

Corrective action

• The controller and the pressure sensor 

head are not correctly connected.

• The pressure sensor head is damaged.

• Connect the controller and the pressure sensor 

head correctly.

• Replace the pressure sensor head.

The load is short-circuited causing an over-

current to flow.

Turn the power OFF and check the load.

Pressure is applied during zero-point adjust-

ment.

Applied pressure at the pressure port should be 

brought to atmospheric pressure and zero-point 

adjustment should be done again. 

External input is carried out outside the rated 

pressure range.

Applied pressure range should be brought within 

the rated pressure range.

Communication error

(Disconnection, faulty connection, etc.)

Check the wiring when using the copy function.

Communication error

(Incorrect model.)

Make sure that the system is configured of the 

same models when using the copy function.

The applied pressure exceeds the upper limit 

of the display pressure range.

Applied pressure range should be brought within 

the rated pressure range.

The output is kept.

The applied pressure exceeds the lower limit 

of the display pressure range.

When other error massage is displayed, contact us.

18

SPECIFICATIONS

Type

NPN output type

PNP output type

For inside of Japan For outside of japan For inside of Japan For outside of japan

Model No.

DPC-L101Z

DPC-L101

DPC-L101Z-P

DPC-L101-P

Applicable pressure 

sensor head

DPH-L113V

DPH-L113

DPH-L133

DPH-L114

DPH-L154

Rated pressure range

-0.1 to 1MPa / 0 to 1MPa / 0 to 3.5MPa / 0 to 10MPa / 0 to 50MPa

Set pressure range

-1.177 to 1.177MPa / -1.070 to 1.070MPa / -3.74 to 3.74MPa / -10.70 to 10.70MPa /

 -53.5 to 53.5MPa

Supply voltage

12 to 24V DC ±10%   Ripple P-P 10% or less

Power consumption

(Note 2)

Normal operation: 960mW or less  (current consumption 40mA or less at 24V supply voltage)

ECO mode (STD): 720mW or less (current consumption 30mA or less at 24V supply voltage)

ECO mode (FULL): 600mW or less (current consumption 25mA or less at 24V supply voltage)

Sensor head supply voltage

Same as supply voltage

Input

Pressure sensor 

head input

Input voltage range: 1 to 5V DC (within the rated pressure range)

External input

• ON voltage: 0.4V DC or less

• OFF voltage: 5 to 30V DC or open

• 

Input impedance: Approx. 10kΩ

• Input time: 1ms or more

• ON voltage: 5V to +V DC

• OFF voltage: 0.6V DC or less or open

• 

Input impedance: Approx. 10kΩ 

• Input time: 1ms or more

Comparative output

(Comparative output 1/2)

NPN open-collector transistor

• Maximum sink current: 50mA

• Applied voltage: 30V DC or less

(between comparative output and 0V)

• Residual voltage: 1V or less 

(at 50mA sink current)

PNP open-collector transistor

• Maximum source current: 50mA

• Applied voltage: 30V DC or less 

(between comparative output and +V)

• Residual voltage: 1V or less

(at 50mA source current)

Output operation

Selectable either N.O. or  N.C., with key operation

Hysteresis

Minimum 1 digit

Repeatability

Within ±0.2% F.S.

Response time

5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms or 5,000ms

selectable with key operations

Analogue output

<Analogue voltage output>

• Output voltage: 1 to 5V

• 

Output impedance: Approx. 1kΩ

• Zero point: Within 1V ±0.5% F.S.

(

DPH-L113V

: Within 1.364V ±0.5% F.S.)

• Span: Within 4V ±0.5% F.S.

• Linearity: Within ±0.1% F.S.

<Analogue current output>

• Output current: 4 to 20mA

• 

Load resistance: 250Ω (MAX.)

• Zero point: within 4mA ±1% F.S.

(

DPH-L113V

: within 5.455mA ±1% F.S.)

• Span: Within 16mA ±1.5%F.S.

• Linearity: Within ±0.1%F.S.

Ambient temperature

-10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60ºC

Ambient humidity

35 to 85% RH, Storage: 35 to 85% RH

Material

Enclosure: PBT (with glass fiber), LCD display: Acrylic

Mounting screw section: Brass (nickel-plated), Switch: Silicon rubber

Weight

(Main body only)

Approx. 25g

Accessories

CN-66A-C2 

(Cable with a connector, 2m long) (Optional for J type): 1 pc.

Unit switching label: 1 pc.

Notes: 1)  The cable with connector is not enclosed with models that have “-J” at the end of the model names.

 

2)  Excluding the current consumption of analogue output current and applying pressure sensor head.

 

3)  The specified value is only for controller. Refer to attached instruction manual of pressure sensor head 

of used as combination for specified value .

Panasonic Industry Co., Ltd.

Panasonic Industrial Devices SUNX Co., Ltd.

https://panasonic.net/id/pidsx/global

Please visit our website for inquiries and about our sales network.

Panasonic Industrial Devices SUNX Co., Ltd. 2022

September, 2022

PRINTED IN JAPAN

Summary of Contents for DPH-L100

Page 1: ...d for com parative output 2 on the sub display Window comparator mode In this mode the ON or OFF state of the comparative output is controlled with a pressure in the set range Notes 1 Hysteresis can be fixed in 8 steps Refer to Hysteresis fixed value selection in PRO MODE for setting 2 or is displayed for comparative output 1 and or is displayed for com parative output 2 on the sub display 3 Set t...

Page 2: ...d for com parative output 2 on the sub display Window comparator mode In this mode the ON or OFF state of the comparative output is controlled with a pressure in the set range Notes 1 Hysteresis can be fixed in 8 steps Refer to Hysteresis fixed value selection in PRO MODE for setting 2 or is displayed for comparative output 1 and or is displayed for com parative output 2 on the sub display 3 Set t...

Page 3: ...d for com parative output 2 on the sub display Window comparator mode In this mode the ON or OFF state of the comparative output is controlled with a pressure in the set range Notes 1 Hysteresis can be fixed in 8 steps Refer to Hysteresis fixed value selection in PRO MODE for setting 2 or is displayed for comparative output 1 and or is displayed for com parative output 2 on the sub display 3 Set t...

Page 4: ...d for com parative output 2 on the sub display Window comparator mode In this mode the ON or OFF state of the comparative output is controlled with a pressure in the set range Notes 1 Hysteresis can be fixed in 8 steps Refer to Hysteresis fixed value selection in PRO MODE for setting 2 or is displayed for comparative output 1 and or is displayed for com parative output 2 on the sub display 3 Set t...

Reviews: