99
16 INSTALLATION (ELECTRIC) AND SERVICE INSTRUCTIONS
A
Turn on power to all air conditioner units.
B
Turn on power to the Intelligent Controller.
C
Set the date and time on the Intelligent Controller and verify the system con
fi
guration.
D
Following the display on the Intelligent Controller, verify the number of units connected.
E
Perform the necessary settings.
Be sure to set the central control address.
●
Give the Operating Instructions to the customer.
●
Explain the operation to the customer, following the explanations given in the Operating Instructions.
(1) External system inputs
(no-voltage contact point static)
DI 1
DI 2
DI 3
All stop input
All start input
(reserved)
Equipment
Keep the input and output signal line lengths to under 65 ft. For distances greater
than this, install a standalone communication adaptor, or use a relay.
For use in areas that may be susceptible to electrical noise, use two-conductor
shielded cable (with one line grounded), with a cross-section of AWG#20 or greater.
Do not apply external voltages to the input terminals.
The input terminals use a sensing current of about 10 mA at 5 V DC.
The output terminal allowable contact voltage and current are 30 V DC, 0.5 A.
(2) External system outputs
(no-voltage contact point static)
(Output common)
All alarm output
All operation output
Equipment
Digital inputs
(3) Pulse meter inputs
(no-voltage contact point pulse)
P1
P2
P3
Gas flow meter
(Fuel flow meter)
Electricity meter 1
Electricity meter 2
Minimum pulse width 100 msec
*1 Factory default setting (alterable)
*1
Minimum pulse interval 1 sec
The Intelligent Controller has a power switch.If the
LCD is blank after connecting power, check the
position of the power switch.
POWER
ON
OFF
Power
supply
terminals
Power
switch
9
S
6
S
S8
S7
D1
D2
UP DOWN SET
HOME
CN32
BA
S1
CN1
3
1
CN2
10
0
19
9
AD
APTOR BO
ARD
7-segment LED
Home key
Up / down /set keys
Termination resistor
jumper for
communication
adaptor control wire
Power supply
terminals
s
l
a
n
i
m
r
e
t
l
a
n
g
i
S
h
c
t
i
w
s
r
e
w
o
P
* Ordinarily, there is no need to change any settings on the Intelligent
Controller board.
DI 1
DI 2
All stop input
All start input
Equipment
Power
supply
terminals
Earth
terminal
Power
switch
OFF
ON
4
Connecting to external equipment
5
Power switch
6
Circuit board diagram
7
Verify the system confi guration, make necessary settings
8
Educating the customer