10.2.13. As To Making The Inspection After Completion Of Work Fully Understood
• At the time when the work has been completed, measure and record the characteristics of test run without fail and keep the
measuring date, etc.
• Carry out the measurement regarding room temperature outside air temperature, suction and air discharge temperatures, wind
velocity, wind volume, voltage current, presence of abnormal vibration, operating pressure, piping temperature, compressive
pressure, airtight pressure as items to be measured.
• As to the structure and appearance, check following items.
10.2.14. As To Delivery To The Customer
• Request the customer to operate this air conditioner viewing instruction manual come with indoor unit in practice and explain
how to operate.
• Deliver the instruction manual to the customer without fail.
NOTE 2
Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.)
Once the cause of the short is eliminated, normal operation will then be possible.
NOTE 3
When running the units in heating mode during test operation, be sure to run the units in cooling mode first before selecting this
mode. If heating mode is selected first, it may cause problems with operation of the compressor.
NOTE 4
Test operation should be carried out for a minimum of 5 minutes. (Test operation will be cancelled automatically after 30
minutes.)
NOTE 5
Test operation mode should always be cancelled once test operation itself has been completed.
NOTE 6
If the self-diagnosis function reports a problem but more than one problem has developed at the indoor and/or outdoor units, the
problem display on the remote control unit may not match the LED display on the outdoor unit printed circuit board. In such
cases, check both locations and remove the causes of the problems.
Short circuit of the blow-out air
Mistake in wiring
Smooth flow of the drain
Reliable connection of the grand wire
Reliable thermal insulation
Looseness in terminal screw, fastening torque
Leakage of refrigerant
M3… 69-98N•cm{7-10kgf•cm} M4…157-196N•cm{16-20kgf•cm}
M5… 196-245N•cm{20-25kgf•cm}
Summary of Contents for CU-YL28HBE5
Page 14: ...14 5 Dimensions 5 1 CU YL24HBE5 CU YL28HBE5 ...
Page 15: ...15 5 2 CU YL34HBE5 ...
Page 16: ...16 5 3 CU YL43HBE5 ...
Page 17: ...17 6 Block Diagram 6 1 CU YL24HBE5 CU YL28HBE5 ...
Page 18: ...18 6 2 CU YL34HBE5 ...
Page 19: ...19 6 3 CU YL43HBE5 ...
Page 20: ...20 7 Wiring Diagram 7 1 CU YL24HBE5 CU YL28HBE5 ...
Page 21: ...21 7 2 CU YL34HBE5 ...
Page 22: ...22 7 3 CU YL43HBE5 ...
Page 23: ...23 8 Electronic Circuit Diagram 8 1 CU YL24HBE5 CU YL28HBE5 ...
Page 24: ...24 8 2 CU YL34HBE5 ...
Page 25: ...25 8 3 CU YL43HBE5 ...
Page 26: ...26 9 Printed Circuit Board 9 1 CU YL24HBE5 CU YL28HBE5 9 1 1 Printed Circuit Board Main ...
Page 27: ...27 9 1 2 Printed Circuit Board Noise Filter 9 1 3 Printed Circuit Board Display ...
Page 28: ...28 9 2 CU YL34HBE5 CU YL43HBE5 9 2 1 Printed Circuit Board Main ...
Page 29: ...29 9 2 2 Printed Circuit Board Capacitor ...
Page 30: ...30 9 2 3 Printed Circuit Board Display Noise Filter ...
Page 56: ...56 11 Technical Data 11 1 Sound Data ...
Page 57: ...57 ...
Page 59: ...59 11 2 1 1 CS F14DB4E5 2 CU YL28HBE5 ...
Page 60: ...60 Cooling capacity curve ...
Page 61: ...61 Cooling power consumption curve ...
Page 62: ...62 11 2 1 2 CS F18DB4E5 2 CU YL34HBE5 ...
Page 63: ...63 Cooling capacity curve ...
Page 64: ...64 Cooling power consumption curve ...
Page 65: ...65 11 2 1 3 CS F24DB4E5 CU YL24HBE5 ...
Page 66: ...66 Cooling capacity curve ...
Page 67: ...67 Cooling power consumption curve ...
Page 68: ...68 11 2 1 4 CS F24DB4E5 2 CU YL43HBE5 ...
Page 69: ...69 Cooling capacity curve ...
Page 70: ...70 Cooling power consumption curve ...
Page 71: ...71 11 2 1 5 CS F28DB4E5 CU YL28HBE5 ...
Page 72: ...72 Cooling capacity curve ...
Page 73: ...73 Cooling power consumption curve ...
Page 74: ...74 11 2 1 6 CS F34DB4E5 CU YL34HBE5 ...
Page 75: ...75 Cooling capacity curve ...
Page 76: ...76 Cooling power consumption curve ...
Page 77: ...77 11 2 1 7 CS F43DB4E5 CU YL43HBE5 ...
Page 78: ...78 Cooling capacity curve ...
Page 79: ...79 Cooling power consumption curve ...
Page 83: ...83 Heating COP curve ...
Page 86: ...86 Heating COP curve ...
Page 89: ...89 Heating COP curve ...
Page 92: ...92 Heating COP curve ...
Page 95: ...95 Heating COP curve ...
Page 98: ...98 Heating COP curve ...
Page 101: ...101 Heating COP curve ...
Page 114: ...114 12 Exploded View and Replacement Parts List 12 1 Outdoor Unit ...
Page 116: ...116 ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 121: ...121 ...
Page 122: ...122 ...
Page 123: ...123 ...