Safety precautions

e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over 

fi

 ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been 

fi

 lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant. To avoid 

fi

 re or 

explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains 

fl

 ammable 

refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of 

fl

 ammable 

refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that 

fl

 ammable refrigerant does not 

remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

English

Summary of Contents for CS-WPU9WKH-8M

Page 1: ...t Operating Instructions Air Conditioner 20 37 Before operating the unit please read these operating instructions thoroughly and keep them for future reference The included Installation Instructions s...

Page 2: ...N 2 3 1 1 K o n p y l ng c a i u khi n 2 L p pin AAA ho c R03 3 y n p A i u ch nh ng h 1 Nh n v t th i gian Nh n v gi n t trong kho ng 5 gi y hi n th th i gian theo 12 gi am pm ho c 24 gi 2 X c nh n S...

Page 3: ...i i th ch v c th kh c so v i m y th c Nh s n xu t c th thay i m kh ng b o tr c nh m m c ch c i ti n s n ph m C m n b n l a ch n M y i u h a kh ng kh Panasonic B C c t nh n ng c b n 2 Nh n MODE ch n ch...

Page 4: ...n ng ch u tr ch nhi m v an to n cho h Kh ng n n tr em ngh ch ch i v i m y Vui l ng li n h v i i l y quy n ho c chuy n gia v sinh c c b ph n b n trong s a ch a l p t th o v l p l i m y L p t v x l kh n...

Page 5: ...ng i u khi n t xa Th o pin kh i i u khi n t xa n u kh ng s d ng trong th i gian d i Pin m i c ng lo i ph i c l p ng c c nh ch d n Ngu n c p i n Kh ng k o d y ngu n ra kh i c m tr nh b gi t i n Ngu n...

Page 6: ...c n b c k n u h b ng k p d y bu c b o qu n R32 gi ng nh b o qu n R410A Vi c v n h nh b o d ng s a ch a v n p l i m i ch t l m l nh ph i c ti n h nh b i c c nh n vi n c o t o v ch ng nh n v ph i c gi...

Page 7: ...x l theo ng quy nh 2 B o tr 2 1 Nh n vi n b o tr H th ng c ki m tra th ng xuy n gi m s t v s a ch a b i nh n vi n b o h nh c o t o v ch ng nh n c thu b i ng i s d ng hay m t t ch c c tr ch nhi m C n...

Page 8: ...g gi ph i m b o ph n t n m i ch t l m l nh c th i ra m t c ch an to n v t t h n l n n th i ra ngo i kh ng kh 2 7 Ki m tra thi t b l m l nh Khi ph i thay i c c thi t b i n ph i s d ng c c thi t b m i p...

Page 9: ...m n c ph i ch u p l c ph c b rung c c c m p s c hay ch u c c t c ng kh c c a m i tr ng hay kh ng Vi c ki m tra c ng c n t nh n nh h ng c a th i gian s d ng c a thi t b hay s rung li n t c t c c ngu n...

Page 10: ...ch h p theo h ng d n m b o r ng h th ng l m l nh c ti p t tr c khi n p m i ch t l m l nh cho h th ng D n nh n l n h th ng khi qu tr nh n p li u ho n t t n u ch a c l m C n ph i h t s c c n tr ng kh n...

Page 11: ...qu tr nh n p m i ch t cho to n h th ng M i b nh ch a c s d ng ph i c quy nh r cho c c m i ch t c thu h i v ph i c d n nh n c n th n cho m i ch t c ngh a l c c b nh ch a c bi t thu h i m i ch t B nh c...

Page 12: ...i u ch nh T C QU T v ch Y N T NH FAN SPEED T C QU T ch AUTO T NG t c qu t s c t ng i u ch nh theo ch ho t ng QUIET Y N T NH Gi m ti ng n c a lu ng gi th i POWERFUL t c nhi t c i t nhanh ch ng Ch n y...

Page 13: ...gian thi t l p kh c nhau Ghi ch SLEEP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO C th c ch n c ng l c C th c k ch ho t m i ch C th c h y b b ng c ch nh n n t m t l n n a Ch POWERFUL QUIET hay FAN SPEED...

Page 14: ...M L NH 26 0 C 28 0 C 79 F 82 F H ng gi ch COOL DRY L M L NH H T M N u thi t l p AUTO T NG c nh o gi s t ng di chuy n l n xu ng i u khi n ch t kh i ng N u i n c kh i ph c sau khi m t i n c c qu tr nh...

Page 15: ...Kh ng ch m v o trong khi m y ang ho t ng L i l c kh 2 tu n m t l n R a tr ng l i l c nh nh ng tr nh l m h b m t l i l c Ph i kh l i l c trong b ng r m tr nh xa l a ho c ph i tr c ti p d i n ng Thay l...

Page 16: ...c c linh ki n b ng nh a s b b c m u nhanh h n khi ti p x c v i nhi t nh s ng m t tr i tia c c t m ho c y u t m i tr ng B i c th b m v o xung quanh b ng i u khi n ph a tr c l i t n nhi t v t ng bao qu...

Page 17: ...ph t ho t ng n u ch nh l ch nhi t gi a c a gi v o v c a gi ra nh d i y c ngh a l m y ho t ng b nh th ng COOL L M L NH 8 C 14 4 F M y s kh ng c s d ng trong m t th i gian d i B t ch nanoeTM G trong 2...

Page 18: ...1 C m bi n h b i c v n H 32 C m bi n nhi t d n trao i nhi t s 2 c a kh i ngo i b t th ng H 33 Kh i trong kh i ngo i m t k t n i v i nhau H 34 C m bi n nhi t b l m m t kh i ngo i b t th ng H 35 N c ng...

Page 19: ...ng nhau K hi u n y c th d ng k t h p v i m t k hi u h a h c Trong tr ng h p n y n tu n th c c quy nh c li n quan v h a ch t B O NG Bi u t ng n y cho bi t thi t b d ng m i ch t l m l nh c th g y ch y...

Page 20: ...1 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press and set the time Press and hold for approximately 5 seconds to show time in 12 ho...

Page 21: ...y differ from the actual unit They are subject to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start st...

Page 22: ...e supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit I...

Page 23: ...long period of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to prevent electric shock nanoe G generat...

Page 24: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use o...

Page 25: ...the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised...

Page 26: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 27: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also...

Page 28: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 29: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 30: ...setting If power failure occurs during this operation this operation will be resumes immediately after power resumes To enjoy freshness and cleaner environment nanoe G nanoe G Indicator To adjust FAN...

Page 31: ...ration is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick Guide 2 sets of ON and OFF timers are available to turn ON or OFF the unit at...

Page 32: ...nergy COOL 26 0 C 28 0 C 79 F 82 F Air flow direction In COOL DRY mode If AUTO is set the flaps swings up down automatically Auto restart control If power is resumed after a power failure the operatio...

Page 33: ...n Air filters Once every 2 weeks Wash rinse the filters gently with water to avoid damage to the filter surface Dry the filters thoroughly under shade away from fire or direct sunlight Replace any dam...

Page 34: ...iscoloration is subject to material types used in plastic parts accelerated when exposed to heat sun light UV light or environmental factor Dust may have collected around the front panel grilles and w...

Page 35: ...tion After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units are not going to be used for a long period...

Page 36: ...heat sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnorma...

Page 37: ...ght be used in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flam...

Page 38: ...Memo...

Page 39: ...Memo...

Page 40: ...Printed in Malaysia ACXF55 26991 SS0220 1 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2020...

Reviews: