9.2.2.
R410A Tools
1. Copper tube gauge for clearance adjustment
(used when flaring with the conventional flaring tool (clutch type))
·
This gauge makes it easy to set the clearance for the copper tube
to 1.0-1.5 mm from the clamp bar of the flaring tool.
Fig. 1 Copper tube gauge for clearance adjustment
2. Flaring tool (clutch type)
·
In the R410A flaring tool, the receiving hole for the clamp bar is
enlarged so the clearance from the clamp bar can be set to 0-0.5
mm, and the spring inside the tool is strengthened to increase the
strength of the pipe-expanding torque. This flaring tool can also be
used with R22 piping, so we recommend that you select it if you are
buying a new flaring tool.
Fig. 2 Flaring tool (clutch type)
3. Torque wrenches
Fig. 3 Torque wrenches
Table 5
Conventional wrenches
R410A wrenches
For 1/4 (opposite side x torque)
17mm X 18 N m (180 kgf cm)
17mm X 18 N m (180 kgf cm)
For 3/8 (opposite side x torque)
22mm X 42 N m (420 kgf cm)
22mm X 42 N m (420 kgf cm)
For 1/2 (opposite side x torque)
24mm X 55 N m (550 kgf cm)
26mm X 55 N m (550 kgf cm)
4. Manifold gauge
·
Because the pressure is higher for the R410A type, the conventional type cannot be used.
Table 6 Difference between R410A and conventional high/low-pressure gauges
Conventional gauges
R410A gauges
High-pressure gauge (red)
-76 cmHg - 35 kgf/cm
-0.1 - 5.3 Mpa
-76 cmHg - 53 kgf/cm
Low-pressure gauge (blue)
-76 cmHg - 17 kgf/cm
-0.1 - 3.8 Mpa
-76 cmHg - 38 kgf/cm
·
The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of refrigerant.
Table 7 Difference between R410A and conventional manifold port size
Conventional gauges
R410A gauges
Port size
7/16 UNF 20 threads
1/2 UNF 20 threads
32
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE
Summary of Contents for CS-VA120KE
Page 5: ...2 2 INDOOR UNIT 5 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 6: ...2 3 OUTDOOR UNIT 6 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 54: ...13 Troubleshooting Guide 54 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 58: ...58 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 59: ...59 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 64: ...15 4 REMOTE CONTROLLER 64 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Page 76: ...MEMO ...
Page 77: ...MEMO ...
Page 78: ...Printed in Japan MS1299SO ...