 Safety Precautions

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since 

fl

 ammability is a consideration. 

The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to 

fi

ll until the working pressure is 

achieved, then venting to atmosphere, and 

fi

nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the 

fi

 nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN = oxygen free nitrogen, type of inert gas.

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant.

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over 

fi

ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid 

fi

 re 

or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
recovered refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 

that: 

• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d) Pump down refrigerant system, if possible.

Summary of Contents for CS-PU9XKT

Page 1: ...660 2 19 Operating Instructions Air Conditioner 20 37 Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer...

Page 2: ...R03 3 A 1 5 12 am pm 24 2 SET AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING SLEEP FAN SPEE...

Page 3: ...3 B 2 MODE DRY AUTO COOL 1 OFF ON OFF ON POWER 3 TEMP 16 0 C 30 0 C 60 F 86 F 10 C F 4 11 12 13 14 15 16 18 19 AAA R03 2 2...

Page 4: ...4...

Page 5: ...5 Ni Cd ELCB RCD ELCB...

Page 6: ...6 R32 Amin A Amin R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A R32 R410A R22 R32 R410A 1 2 R32 R410A a b c d e...

Page 7: ...7 f g h i j 5 0 25 1 04MPa 4 15MPa 1 Amin A 12 2 2 1 2 2 2 2 2 8 2 2...

Page 8: ...8 2 3 2 4 CO2 2 5 2 6 2 7 2 8...

Page 9: ...9 7 5 0 25 1 04 4 15 LFL 25 OFN 8 3 4 5 6...

Page 10: ...10 9 OFN 7 10 a b c d 8 OFN OFN OFN OFN...

Page 11: ...11 e f g h 80 i j k 11 12 Waste Transfer Note...

Page 12: ...DITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QUIET POWERFUL ECO AIR SWING FAN SPEED AUTO FAN QUIET FAN SPEED QUIET POWER TIMER ECO POWERFUL 4 ECO POWERFUL ECO POW...

Page 13: ...0 5 1 2 3 4 5 6 7 8 9 0 0 SLEEP SLEEP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO POWERFUL QUIET FAN SPEED ON OFF SET TIMER CANCEL 1 2 3 1 TIMER ON TIMER OFF 22 00 OFF 2 3 SET ON OFF CANCEL ON OFF SET...

Page 14: ...14 AUTO COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY COOL DRY C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT...

Page 15: ...15 H 99 pH 7 40 C 104 F 2 1 2 AUTO OFF ON ECO 1 2 3 4 2 ECO AUTO OFF ON...

Page 16: ...16 POWER ON 15 TIMER 2 3 UV COOL...

Page 17: ...17 AUTO OFF ON 1 2 AUTO OFF ON AUTO 3 AUTO OFF ON 1 COOL 4 AUTO OFF ON 5 AUTO OFF ON COOL 15 COOL 8 C 14 4 F...

Page 18: ...12 H 14 H 15 H 16 CT H 17 H 19 H 21 H 23 1 H 24 2 H 25 H 26 H 27 H 28 1 H 30 H 31 H 32 2 H 33 H 34 H 35 H 36 H 37 H 38 H 39 H 41 H 50 H 51 H 52 H 58 H 59 H 64 H 67 H 70 H 71 H 72 H 85 LAN H 97 H 98 H...

Page 19: ...19 Pb...

Page 20: ...e back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or...

Page 21: ...approximately 10 seconds to show the temperature as C or F Thank you for purchasing Panasonic Air Conditioner Table of Contents Safety Precautions 22 29 How to Use 30 31 To Learn More 32 Cleaning the...

Page 22: ...e supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit I...

Page 23: ...unit is not going to be used for a long period of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to prev...

Page 24: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use o...

Page 25: ...the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised...

Page 26: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 27: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 28: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 29: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 30: ...an speed is adjusted automatically according to the operation mode QUIET This operation reduces airflow noise FAN SPEED QUIET POWERFUL To reach the desired temperature quickly This operation is automa...

Page 31: ...CO FAN SPEED QUIET POWERFUL ECO Can be selected at the same time Can be activated in all modes POWERFUL QUIET and FAN SPEED cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL...

Page 32: ...zontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Auto...

Page 33: ...id damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Remove from the unit Insert into the...

Page 34: ...n the discharged cold air may condense to water vapour Outdoor unit emits water or steam During cooling operation condensation occurs on cold pipes and the condensed water may drip from the outdoor un...

Page 35: ...unit to select COOL mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference bet...

Page 36: ...heat sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnorma...

Page 37: ...ght be used in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flam...

Page 38: ...Memo...

Page 39: ...Memo...

Page 40: ...Printed in Malaysia ACXF55 31660 SS0921 0 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021...

Reviews: