e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over 

fi

 ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been 

fi

 lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.To avoid 

fi

 re or 

explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains 

fl

 ammable 

refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of 

fl

 ammable 

refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that 

fl

 ammable refrigerant does not 

remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

Safety precautions

ACXF55-23440_YA1218-0.indb   27

ACXF55-23440_YA1218-0.indb   27

11/29/2018   9:20:48 AM

11/29/2018   9:20:48 AM

Summary of Contents for CS-PN9VKT

Page 1: ...ating the unit please read these operating instructions thoroughly and keep them for future reference The included Installation Instructions should be kept and read by the installer before installatio...

Page 2: ...NER ON OFF SET TIMER CANCEL OFF ON TEMP OFF ON MODE SLEEP QUIET AIR SWING FAN SPEED AIR CONDITIONER ON OFF TIMER CANCEL SLEEP QUIET AIR SWING FAN SPEED A B ACXF55 23440_YA1218 0 indb 2 ACXF55 23440_YA...

Page 3: ...12 13 14 15 16 17 AAA R03 2 2 2 MODE DRY iAUTO COOL 1 OFF ON OFF ON POWER 3 TEMP 16 C 30 C 60 F 86 F 10 C F ACXF55 23440_YA1218 0 indb 3 ACXF55 23440_YA1218 0 indb 3 11 29 2018 9 20 38 AM 11 29 2018 9...

Page 4: ...4 ACXF55 23440_YA1218 0 indb 4 ACXF55 23440_YA1218 0 indb 4 11 29 2018 9 20 39 AM 11 29 2018 9 20 39 AM...

Page 5: ...5 ELCB RCD ELCB Ni Cd ACXF55 23440_YA1218 0 indb 5 ACXF55 23440_YA1218 0 indb 5 11 29 2018 9 20 39 AM 11 29 2018 9 20 39 AM...

Page 6: ...min A Amin R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A R32 R410A R22 R32 R410A 1 2 R32 R410A a b c d e ACXF55 23440_YA1218 0 indb 6 ACXF55 23440_YA1218 0 indb 6 11 29 2018 9 20 39 AM 11 29 2018 9 20...

Page 7: ...7 f g h i j 5 0 25 1 04MPa 4 15MPa 1 Amin A 12 2 2 1 2 2 2 2 2 8 2 2 ACXF55 23440_YA1218 0 indb 7 ACXF55 23440_YA1218 0 indb 7 11 29 2018 9 20 40 AM 11 29 2018 9 20 40 AM...

Page 8: ...8 2 3 2 4 CO2 2 5 2 6 2 7 2 8 ACXF55 23440_YA1218 0 indb 8 ACXF55 23440_YA1218 0 indb 8 11 29 2018 9 20 40 AM 11 29 2018 9 20 40 AM...

Page 9: ...9 3 4 5 6 7 5 0 25 1 04MPa 4 15MPa LFL 25 OFN 8 ACXF55 23440_YA1218 0 indb 9 ACXF55 23440_YA1218 0 indb 9 11 29 2018 9 20 40 AM 11 29 2018 9 20 40 AM...

Page 10: ...10 8 OFN OFN OFN OFN 9 OFN 7 10 a b c d ACXF55 23440_YA1218 0 indb 10 ACXF55 23440_YA1218 0 indb 10 11 29 2018 9 20 40 AM 11 29 2018 9 20 40 AM...

Page 11: ...11 e f g h 80 i j k 11 12 Waste Transfer Note ACXF55 23440_YA1218 0 indb 11 ACXF55 23440_YA1218 0 indb 11 11 29 2018 9 20 40 AM 11 29 2018 9 20 40 AM...

Page 12: ...AIR SWING POWER TIMER i AUTO QUIET AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON TEMP OFF ON MODE SLEEP QUIET AIR SWING FAN SPEED QUIET i AUTO 1 C 2 F 4 ACXF55 23440_YA1218 0 indb 12 ACXF55 23440_YA1...

Page 13: ...3 4 5 6 7 8 9 0 0 SLEEP CANCEL ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 ON OFF 22 00 OFF 2 3 SET ON OFF CANCEL SET SET ACXF55 23440_YA1218 0 indb 13 ACXF55 23440_YA1218 0 indb 13 11 29 2018 9 20 41 AM...

Page 14: ...79 F 82 F i AUTO COOL DRY AUTO C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 43 109 4 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT ACXF55 23440_YA1218 0 indb 14 ACXF55 23440_YA1218 0 indb 14 11 29 2018...

Page 15: ...15 6 1 2 1 2 2 3 4 pH 7 40 C 104 F 2 10 CZ SA22P ACXF55 23440_YA1218 0 indb 15 ACXF55 23440_YA1218 0 indb 15 11 29 2018 9 20 43 AM 11 29 2018 9 20 43 AM...

Page 16: ...16 POWER 15 TIMER COOL ACXF55 23440_YA1218 0 indb 16 ACXF55 23440_YA1218 0 indb 16 11 29 2018 9 20 44 AM 11 29 2018 9 20 44 AM...

Page 17: ...17 AUTO OFF ON 1 2 i AUTO 3 1 COOL 4 5 OFF ON COOL 15 COOL 8 C 14 4 F TIMER ACXF55 23440_YA1218 0 indb 17 ACXF55 23440_YA1218 0 indb 17 11 29 2018 9 20 44 AM 11 29 2018 9 20 44 AM...

Page 18: ...roximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm SET Use remote control within 8 m from the remote control receiver of the indoor unit 8 AIR CONDITIONER ON OFF SET TI...

Page 19: ...p Down TEMP Selection range 16 C 30 C 60 F 86 F Press and hold for approximately 10 seconds to switch the temperature indication in C or F Thank you for purchasing Panasonic Air Conditioner The illust...

Page 20: ...se leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst...

Page 21: ...s may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoid injury etc...

Page 22: ...0A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any per...

Page 23: ...ys contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who...

Page 24: ...Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If...

Page 25: ...ot be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration f...

Page 26: ...kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when charging is complete...

Page 27: ...g the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cy...

Page 28: ...max 4 hours the set temperature follows the last set temperature setting Fan speed is fixed at AUTO fan speed selection is prohibited During unit is off press will turn on the unit with i AUTO mode i...

Page 29: ...tting please refer to Quick guide To turn ON or OFF the unit at a preset time To maximise comfort while sleeping SLEEP CANCEL This operation provides you with a comfortable environment while sleeping...

Page 30: ...izontal flap are fixed at the predetermined position Auto restart control If power is resumed after a power failure the operation will restart automatically after a period of time with previous operat...

Page 31: ...2 Pull out and lift up Close it securely 2 Push in 1 Insert at both sides 3 Close down 4 Press both ends and center of the front panel Air filters Once every 2 weeks Wash rinse the filters gently with...

Page 32: ...cooling process Outdoor unit emits water steam Condensation or evaporation occurs on pipes Discoloration of some plastic parts Discoloration is subject to material types used in plastic parts accelera...

Page 33: ...ration it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units are not going to be used for a long period of time Turn off the power...

Page 34: ...Memo ACXF55 23440_YA1218 0 indb 34 ACXF55 23440_YA1218 0 indb 34 11 29 2018 9 20 52 AM 11 29 2018 9 20 52 AM...

Page 35: ...Memo ACXF55 23440_YA1218 0 indb 35 ACXF55 23440_YA1218 0 indb 35 11 29 2018 9 20 52 AM 11 29 2018 9 20 52 AM...

Page 36: ...an Union These symbols are only valid in the European Union If you wish to discard these items please contact your local authorities or dealer and ask for the correct method of disposal Pb Note for th...

Reviews: