29
11.2.3.
Indoor Unit
11.2.3.1. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The center of installation plate should be at more than 550 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the center of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole center is obtained
by measuring the distance namely 150 mm and 125 mm
for left and right hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.2.3.2. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.2.3.3. INDOOR UNIT INSTALLATION
1.
For the right rear piping
2.
For the right and right bottom piping
: For left side piping, piping connection for liquid should be about
126 mm from this line.
: For left side piping, piping connection for gas should be about
174 mm from this line.
: For left side piping, piping connection cable should be about
984 mm from this line.
Caution
When the wall is hollow, please be sure to use the sleeve
for tube ass’y to prevent dangers caused by mice biting
the connecting cable.
Summary of Contents for CS-PC18GKF
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 ...
Page 13: ...13 6 Refrigeration Cycle Diagram ...
Page 14: ...14 7 Block Diagram ...
Page 15: ...15 8 Wiring Connection Diagram ...
Page 16: ...16 ...
Page 17: ...17 9 Electronic Circuit Diagram ...
Page 18: ...18 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Page 19: ...19 ...
Page 20: ...20 10 2 Power Printed Circuit Board ...
Page 21: ...21 10 3 Indicator panel ...
Page 49: ...49 16 Technical Data 16 1 Thermostat Characteristics ...
Page 50: ...50 16 2 Operation Characteristics CS PC18GKF CU PC18GKF ...
Page 51: ...51 ...
Page 52: ...52 CS PC24GKF CU PC24GKF ...
Page 53: ...53 ...
Page 55: ...55 ...
Page 56: ...56 CS CU PC24GKF ...
Page 57: ...57 16 5 Sound Data CS PC18GKF ...
Page 58: ...58 CS PC24GKF ...