15.4.19 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error code will not display (no TIMER LED blinking) but store in EEPROM
Malfunction Decision Conditions
•
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
•
Clogged air filter of the indoor unit
•
Dust accumulation on the indoor unit heat exchanger
•
Air short circuit
•
Detection error due to faulty indoor pipe temperature sensor
•
Detection error due to faulty indoor unit PCB
Troubleshooting
When abnormality indication starts again
Is the air filter dirty?
●
Clean the air filter
Check the air filter
Is the indoor unit heat exchanger dirty?
●
Clean the indoor unit heat
exchanger
Is there any short circuit?
Check the air passage
YES
●
Provide sufficient air passage
NO
Does it conform to the sensor characteristic chart?
Check the indoor heat exchanger temperature
sensor
●
Replace the indoor unit PCB
●
Defect in indoor unit PCB
●
Replace the indoor unit PCB
Check the dust accumulation on the indoor unit heat
exchanger
NO
NO
YES
YES
YES
NO