13.5.23 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling, when an input over-current (X value in Total Running Current Control) is detected by
checking the input current value being detected by current transformer (CT) with the compressor running.
Malfunction Caused
Excessive refrigerant.
Faulty outdoor unit PCB.
Troubleshooting
Turn off power supply. Check the main
circuit electrolytic capacitor
When F98 indication happens
Get restarted and measure the input
current
NO
Is Input current > specification?
●
Replace the outdoor unit PCB
NO
YES
Normal?
Check refrigerant amount
●
Repair the pipe flare or union nuts
Reclaim and recharge refrigerant
●
Reclaim and recharge with correct
amount of refrigerant
Excess refrigerant?
YES
NO
YES
NO
●
Replace outdoor unit PCB
●
Replace outdoor unit compressor
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Caution