10
Model
Indoor/Outdoor
CS-MPS24SKH / CU-3S28SBH
Performance Test Condition
JIS
Power Supply
Phase, Hz
Single, 50
V
220
240
Min.
Mid.
Max.
Cooling
Capacity
kW
1.90
6.00
6.20
BTU/h
6480
20500
21100
kJ/h
6840
21600
22320
Running Current
A
9.30
8.60
Input Power
W
400
1.92k
2.07k
EER
W/W
4.75
3.13
3.00
kJ/hW
17.10
11.25
10.78
Indoor Noise (H / L / QLo)
dB-A
48 / 39 / -
Indoor
F
an
Type
Cross-flow fan
Material
ASG30K1
Motor Type
DC / Transistor (8 poles)
Input Power
W
94.8
Output Power
W
40
Speed
Lo
rpm
1000
Me
rpm
1200
Hi
rpm
1400
Moisture Removal
L/h
3.3
Indoor Airflow
Lo
m
3
/min (ft
3
/m)
12.23 (432)
Me
m
3
/min (ft
3
/m)
15.37 (543)
Hi
m
3
/min (ft
3
/m)
18.50 (655)
Dimension
Height (I/D)
mm (inch)
290 (11-7/16)
Width (I/D)
mm (inch)
1070 (42-5/32)
Depth (I/D)
mm (inch)
240 (9-15/32)
Weight
Net (I/D)
kg (lb)
12 (26)
Piping
Pipe Diameter
(Liquid / Gas)
mm (inch)
6.35 (1/4) / 12.70 (1/2)
Drain Hose
Inner Diameter
mm
16.2
Length
mm
550
Indoor Heat
Exchanger
Fin Material
Aluminium (Pre coated)
Fin Type
Slit Fin
Row x Stage x
FPI
2 x 15 x 21
Size (W x H x L)
mm
810 x 315 x 25.4
Air Filter
Material
Polypropelene
Type
One-touch
Power Supply
Outdoor
Power Supply Cord
A
-
Thermostat
-
Protection Device
-
DRY BULB
WET BULB
Indoor Operation Range
Maximum °C
32
23
Minimum °C
16
11
1.
Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
2.
Specifications are subject to change without notice for further improvement.