Panasonic CS-ME10CB1P Service Manual Download Page 36

Liquid side

Gas side

ø 6.35 (1/4") t 0.8

ø 9.52 (3/8") t 0.8

CAUTION

When the wall is hollow, 
please be sure to use the 
sleeve for tube ass'y to 
prevent dangers caused by 
mice biting the connecting 
cable. 

Attaching the remote control holder to the wall

1

2

6

3

4

5

7

8

10

9

11

12

Indoor Unit Accessory Parts

1

2

1

2

1

1

2

1

1

1

2

2

Required Materials

• Read the catalog and other technical materials and prepare the required materials.

Product name                                                    Remarks

VP20 (outer diameter ø26); also sockets, 
elbows and other parts as necessary

PVC adhesive

For refrigerant piping insulation (foamed 
polyethylene with a thickness of 8 mm or more)
For drain piping insulation (foamed polyethylene 
with a thickness of 10 mm or more)

×

 1.5 mm

2

 flexible cord, type designation 

245 IEC 57 (H05RN-F)

Hanging bolts (M10) (4) and nuts (12), Flat 
washers (8) (when hanging the indoor unit)  

Rigid PVC pipe

Adhesive

Insulation
  

Indoor/outdoor connecting cable

Hanging bolt related parts

Other Items to be Prepared (Locally Purchased)

Take into consideration the following contents when creating the blueprint.

Indoor unit installation location

Remote control mounting location

The location should be strong enough to support the main unit 
without vibration.
There should not be any heat or steam sources nearby.
Drainage should be easy. Avoid locating the drain port close to 
ditches (domestic wastewater).
Avoid locations above entrances and exits.
Do not block the intake and discharge.
Select the location so that the cool and warm air spreads 
throughout the entire room.
Locate the indoor unit at least 1 m or more away from a TV, radio, 
wireless equipment, antenna cables and fluorescent lights, and 2 
m or more away from a telephone.

Note that if the air conditioning unit is installed near an 
electronically lit fluorescent light (inverter, rapid start type, etc.), 
it may not receive the remote control signals.

Signals may not be transmitted and received correctly when 
the remote control is operated while in the holder. Take the 
remote control in your hand to operate the unit.
Mount the holder in a location that is not subject to the 
effects of heat (direct sunlight and stoves, etc.).

Selecting the Installation Location

1

Selecting the Piping

2

To Drill a Hole in the Wall and 
Install a Sleeve of Piping

3

1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes 

about 15 mm from the wall.

4. Finish by sealing the sleeve with 

putty or caulking compound at the 
final stage. 

• Prepare the piping set shown in the table 

below or equivalent products for the 
refrigerant piping.

* See the Outdoor Unit Installation 
  Instructions.

Remote control holder
fixing screws 

Remote control 
holder

Remote
control  3

5

6

Bushing for 
tube ass'y 

15 mm

Outdoor

Indoor

Wall

Sleeve for 

tube ass'y

ø70 through 
hole

Putty or caulking 
compound

Approx. 
5 - 7 mm

Piping 
insulation

Band

Remote control

Battery

Remote control holder

Drain hose insulation   

Receiver

Remote control holder  
fixing screw

Receiver cover

Clamp 

Clamp mounting screw

Receiver mount

No.

No.

Accessory part

Accessory part

Qty.

Qty.

CS
-M

E

7C

B

1P
/

C

S

-M

E

10CB1

P

/

CS
-M
E

12CB1

P

/

CS
-M
E

14CB1

P

/

CS
-M
E

10CD3

P

/

CS
-M

E

14

CD3P

36

Summary of Contents for CS-ME10CB1P

Page 1: ...S ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P 5 1 Cassette Type 8 5 2 Grille 10 5 3 Duct Type 11 6 Refrigeration Cycle Diagram 12 7 Block Diagram 13 8 Wiring Diagram 14 8 1 Cassette Type CS ME7CB1P ME10CB1P ME12CB1P ME14CB1P 14 8 2 Duct Type CS ME10CD3P ME14CD3P 15 Multi Air Conditioner Please file and use this manual together with the service manual for Model No CS ME7CKPG CS ME10CKPG CS ME12CKP...

Page 2: ...pe 35 11 Operating Instructions 41 12 Disassembly of Parts 53 12 1 Cassette Type Indoor Unit CS ME7CB1P ME10CB1P ME12CB1P ME14CB1P 53 12 2 Duct Type Indoor Unit CS ME10CD3P ME14CD3P 57 13 Technical Data 59 13 1 OPERATION CHARACTERISTICS 59 14 Electronic Circuit Diagram 63 14 1 REMOTE CONTROL 63 14 2 Cassette Type 64 14 3 Duct Type 65 15 Exploded View Replacement Parts List 66 15 1 CS ME7CB1P ME10C...

Page 3: ...2 Three CS ME14CB1P only Total nominal cooling capacity is 12 0kW Inverter controlled for High energy efficiency and optimal comfort New refrigerant R410A is used for protecting ozone layer Lead free P C Board 2 About Lead Free Solder PbF 2 1 DISTINCTION OF PbF P C BOARD P C Boards manufactured using lead free solder will have a PbF stamp on the P C Board 2 2 CAUTION Pb free solder has a higher me...

Page 4: ...3 Functions 3 1 REMOTE CONTROL 4 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 5: ...3 2 INDOOR UNIT 5 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 6: ...6 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 7: ...Weight kg 9 8 10 5 16 5 Fan Type Cross flow fan Sirocco fan Motor Type DC brushless motor EHOCM24A4P25 DC brushless motor ARW31V8P30AC Output W 4P 25W 40V A98258 8P 30W 280 340V A981071 Heat exchanger Plate fin forced draft Adjustments Switches Wireless remote control Timer Timer with ON and OFF times programmable Temperature Electronic thermostat Air filter PP honeycomb Remarks The specifications...

Page 8: ...5 Dimensions 5 1 Cassette Type 8 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 9: ...9 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 10: ...5 2 Grille 10 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 11: ...5 3 Duct Type 11 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 12: ...6 Refrigeration Cycle Diagram 12 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 13: ...7 Block Diagram CS ME7CB1P ME10CB1P ME12CB1P ME14CB1P ME10CD3P ME14CD3P 13 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 14: ...8 Wiring Diagram 8 1 Cassette Type CS ME7CB1P ME10CB1P ME12CB1P ME14CB1P 14 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 15: ...8 2 Duct Type CS ME10CD3P ME14CD3P 15 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 16: ...s not discharged While a heating operation is in progress a cooling operation cannot be performed by an indoor unit in another room In the room where the operation button for heating was pressed first operation is continued In the room where the operation button for cooling was pressed afterward the operation lamp of the indoor unit blinks where the attempt is made to establish the cooling operati...

Page 17: ...on and other operating conditions Cooling and Dry Heating The louver stops at the CLOSE position when the power switch or breaker is ON The louver stops at their current position when the power switch or breaker is OFF Move the horizontal airflow direction control louver manually 17 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 18: ...w fan speed changes depending on the setting made with the FAN SPEED button and other operating conditions Actual fan speed may differ from that you set with remote control 18 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 19: ...19 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 20: ...onds as long as the unit is operating Operation while the unit is off is determined by the difference between the temperature setting and the room temperature Float switch operation When the float switch turns on for 10 seconds continuously the thermostat of the indoor unit turns off and the drain pump operates continuously When the float switch stays on for 150 seconds continuously the drain pump...

Page 21: ...airflow direction before the power is turned off are restored 2 In the case of automatic operation after the power is restored operation starts with the determination of the mode 3 While the air conditioner odour clear timer has been set the setting is cancelled and operation is transferred to the mode before the power is turned off 4 While the air conditioner odour clear operation with timer with...

Page 22: ... cooling operation Press the auto button about 5 8 seconds 1 beep sound to perform the forced cooling operation The air conditioner does not operate for 2 minutes if the room temperature is low intake temperature below 16 C so just wait The forced operation is performed after the 2 minutes have elapsed 3 Forced heating operation Press the auto button about 8 11 seconds 2 beeps sound to perform the...

Page 23: ...he short beep this will achieve A setting 3 After 60 seconds or longer of the above setting use the B set remote control to confirm successful operation 4 Set A B C or D transmission code at remote control Fig 1 5 Odour clear setting mode The odour clear inhibit mode is established by pressing the AUTO button 16 21 seconds 4 beeps sound 6 Individual setting mode The H14 error detection selection m...

Page 24: ...e DRAIN TEST switch to operate it for about 5 minutes 9 6 3 High Static Pressure Switch High state switch SW2 For Duct Type To increase the fan speed open the control box and on the control board switch the HIGH STATE switch SW2 to HI 24 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 25: ... Operation is stopped automatically 2 The timer lamp of the display unit on the indoor unit blinks 3 The timer lamp goes off when the power is turned off To display the trouble or protection operation status stored in the memory 1 Turn on the power 2 Open the remote control unit s door and press the timer setting UP ARROW button for 5 seconds 3 Press the UP ARROW button slowly and repeatedly until...

Page 26: ...ected continuously for 25 seconds or when a state in which the fan motor speed is not synchronized with the control signal has been detected on 7 successive occasions The trouble display appears the timer lamp blinks Diagnosis checkpoint 1 Check the nature of the fan lockup trouble 2 Check for disconnections of the fan motor connectors and for defects in contact in the fan motor and in the control...

Page 27: ...lay appears when a temperature of under 45 C or above 149 C has been detected by the outdoor unit liquid side pipe temperature sensor continuously for 2 seconds Diagnosis checkpoint 1 This trouble display appears when a temperature which is impossibly high or low from a normal standpoint has been detected Check the sensor and if open circuiting more than 500 kΩ or short circuiting less than 0 5 kΩ...

Page 28: ...d back on As the symptom F93 is stored in the memory 30 seconds after the compressor has started up and operation stops The trouble display appears after 4 restarts 3 Check for broken wires open circuits in the compressor winding Approximately 1 ohm under normal conditions for each phase same symptom as in 2 4 Check the power supply voltage has been fluctuating or not F91 Refrigeration cycle abnor...

Page 29: ... fan may be defective The fan will not run because of an open circuit The protection function may be activated by an overload and the F97 trouble display will remain stored in the memory F98 Total running current protection When the total current exceeds the setting 17A to 20A frequency control is started and if it then exceeds the setting operation stops and the trouble display appears Diagnosis ...

Page 30: ...lation instruction An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 3 Carry out drainage piping as mentioned in installation instructions If drainage is not perfect water may enter the room and damage the furniture 7 Wire routing must be properly arranged so that control boar...

Page 31: ...pment antenna cables and fluorescent lights and 2 m or more away from a telephone Note that if the air conditioning unit is installed near an electronically lit fluorescent light inverter rapid start type etc it may not receive the remote control signals To Drill a Hole in the Wall and Install a Sleeve of Piping Indoor Unit Installation Diagram Part name Part number Decorative grille CZ BT20P whit...

Page 32: ...mensions Hanging bolt pitch dimensions Main unit dimensions Ceiling depth dimension 1070 460 1010 390 830 240 H185 W770 D360 190 or more Attach the nuts and washers to the hanging bolts then lift up and hook the main unit onto the hanging fixtures Adjust the lower surface of the indoor unit relative to the ceiling surface as shown in the illustration below Check the levelness using a level or a vi...

Page 33: ...necting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 1 5 mm2 flexible cord type designation 245 IEC 57 H05RN F or heavier cord Ensure the color of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the sli...

Page 34: ... the starting of Test Run operation When installing two air conditioners in one room each air conditioner can be synchronized to the remote control In order to operate separately open the rear cover of one of the remote control and set to B Setting the air conditioner unit to B 1 Press the AUTO switch for about 11 to 15 seconds When you hear three short beeps release the switch 1 Note you will hea...

Page 35: ...n An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 3 Carry out drainage piping as mentioned in installation instructions If drainage is not perfect water may enter the room and damage the furniture 7 Wire routing must be properly arranged so that control board cover is fixed ...

Page 36: ...cool and warm air spreads throughout the entire room Locate the indoor unit at least 1 m or more away from a TV radio wireless equipment antenna cables and fluorescent lights and 2 m or more away from a telephone Note that if the air conditioning unit is installed near an electronically lit fluorescent light inverter rapid start type etc it may not receive the remote control signals Signals may no...

Page 37: ... capable of supporting the unit weight Consult your construction or interior contractor for details on finishing the ceiling opening Fit the drain hose insulation 7 around the drain hose as shown in the right figure Attach the discharge chamber 10 screws Cut out the intake cut out portions in the unit rear panel using cutter or other tools to make openings Remove the two screws at the rear edge of...

Page 38: ...llation in the Ceiling Mounting Section View Securing the Hanging Bolts Reinforced concrete Unit mm Hanging bolt pitch 990 Wooden or other structure Unit mm To increase the air volume open the control box and on the control board switch the high state switch SW2 to HI See the diagram for Connecting the Indoor Outdoor Connecting Cable Switching the high state switch SW2 Hanging bolt M10 Locally Pur...

Page 39: ...oximately 5 minutes and then stops automatically See the diagram for Connecting the Indoor Outdoor Connecting Cable 18N m 1 8 kgf m 42N m 4 2 kgf m Connecting the Drain Piping 5 6 Connecting the Indoor Outdoor Connecting Cable 7 Connecting and Insulating the Refrigerant Piping Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 1 5 mm2 flexible cord t...

Page 40: ...th sec in order to identify the starting of Test Run operation When installing two air conditioners in one room each air conditioner can be synchronized to the remote control In order to operate separately open the rear cover of one of the remote control and set to B Setting the air conditioner unit to B 1 Press the AUTO switch for about 11 to 15 seconds When you hear three short beeps release the...

Page 41: ...llowing items carefully read the operating instructions attached at the outdoor unit for model CS ME7CKPG SAFETY PRECAUTION Installation precautions Operation precautions POINTS TO NOTE Names of parts and preparations Outdoor unit Remote control Operational setup CONVENIENCE OPERATIONS Powerful operations Quiet operations Timer setting Sleep Timer Mode Odour wash mode HELPFUL INFORMATION Inspectio...

Page 42: ...he operation light will light up During Heating Cooling Dry operating mode you may not get an instant air flow TO STOP OPERATION Press one more time Please also refer to Fan speed Air swing Adjustment chapters SETTING TEMPERATURE Setting range 16 30 C Each press on the button will change by 1 C Continuously pressing the button will speed up the changes INCREASE DECREASE RECOMMENDED TEMPERATURE Sel...

Page 43: ...indication lamp green Model number If there is a power failure operation will be automatically restarted under the previous operation mode and air flow direction when power is resumed When the operation is not stopped by remote control If you do not want the unit to restart automatically when power is resumed switch off the main power supply Auto Restart Control is not available when Timer or Slee...

Page 44: ... pressing the button for about 5 seconds a Beep sound will be heard Force control for cooling operations is selected It is not recommended under normal circumstances DRAIN TEST button Used only when installing Not used normally To open Press in the 3 places shown To close Press in the 3 places shown Release lever Cassette Type 44 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD...

Page 45: ...is not stopped by remote control If you do not want the unit to restart automatically when power is resumed switch off the main power supply Auto Restart Control is not available when Timer or Sleep mode is set or the dry mode timer is cancelled Auto Restart Control Receiver unit AUTO OPERATION BUTTON When not using the remote control Continuously pressing the button for about 5 seconds a Beep sou...

Page 46: ...rom the auto air swing Continuously pressing The indication will change accordingly The indications are just air flow direction guidelines which may differ with the actual indoor unit louvre positions and angles Press Press AUTOMATIC FAN SPEED HEATING Fan speed will be running in the Low fan speed when the air temperature is low Fan speed will be running in the High fan speed when the air temperat...

Page 47: ... louvres will automatically close up the air flow outlet vents The louvres will automatically adjust its air flow angles to prevent condensation during COOLING DRY and cold air blowing out during HEATING The louvres adjustment range during HEATING and COOLING DRY may not be the same You can adjust the louvres in 5 steps within these ranges You cannot change the air flow direction on the duct type ...

Page 48: ...r may build up The maintenance period may be used as a criterion However if operating conditions cause build up of odours you need to service it as soon as possible NOTE ITEMS SOLD SEPARATELY PART NAME PART NUMBER Air filter CWD00228 4 Installing the air filter Press in the 3 places shown to close the intake grille Push Push Push Push Push Push Caution Ensure that the operation is stopped power su...

Page 49: ...e mild kitchen detergent neutral type to wash off stubborn dirt and grime Avoid drying the panel in direct sunlight or over a stove May cause color fading and structural distortions 3 To fix the intake grille Cassette Type Release the string from the intake grille Release lever Fit the grille to the hinge on the right of the main unit Slide and hold the release lever in place then fit the grille i...

Page 50: ...for 5 seconds 3 alphanumeric digits will appear on the remote control display 2 When the indoor unit gives off a continuous Beep Beep Beep Beep sound slowly and repeatedly press Inform your dealer on the displayed 3 alphanumeric digits DISPLAYED ALPHANUMERIC DIGITS H F The H and F followed by 2 numerals represent different sets of abnormalities When H33 H36 and H37 are displayed you must not opera...

Page 51: ...fficiency of the unit When the unit is not operated for an extended period of time When there is a power failure During operation All operations stopped When power supply is restored run operations all over again During preset timer mode The timer mode is cancelled The indoor unit TIMER lamp will be off When power supply is restored reset TIMER once again When there is thunder in the vicinity To a...

Page 52: ... the equipment from the main power supply in case of an emergency Notes If the unit is not going to be used for an extended period of time turn off the main Power supply If it is left at the ON position approximately 14 W of electricity will be used even if the indoor unit has been turned off with the remote control If operation is stopped then restart immediately the unit will resume operation on...

Page 53: ...t grille 3 Loosen the screw on the cover and detach the cover 4 Unscrew the 2 screws on the control section cover 5 Detach the connectors going from the control board to the drain pump and from the receiver and display sections 6 Unscrew the screw and disengage the 2 catches on the air outlet grille then take out the drain pan plug to drain off excess water 7 Unscrew the 4 screws and disengage the...

Page 54: ... 10 Loosen the screw fixing the shaft between the cross flow fan and the fan motor and detach the fan motor 11 Remove the cross flow fan 12 1 2 Detaching the drain pump 8 Unscrew the screw on the drain pump holder and detach it 9 Detach the drain hose from the drain pump and remove the drain pump 54 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 55: ...n disengage the catches with a screwdriver and detach the front grille 3 Loosen the screw on the cover and detach the cover 4 Unscrew the 2 screws on the control section cover and detach all connectors 5 Disengage the catch on the control board and remove it 55 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 56: ...ntrol section cover and detach the connector for the louver motor 5 Unscrew the screw and disengage the 2 catches on the air outlet grille 6 Unscrew the 2 screws on the louver motor on the back of the air outlet grille and remove the louver motor 56 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 57: ...etach them 12 2 2 Detaching the control board 1 First detach the upper and inner casing 12 2 1 2 Unscrew the 2 screws on the slide guide 3 Pull the board down following the slide guide 4 Lift the control board up from the bottom disengage the catch holding the board and open it 57 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 58: ...nd fan loosen the screw holding the fan and detach the fan 12 2 4 Detaching the fan motor and drain motor Fan motor 1 First detach the upper and inner casing 12 2 1 and the fan 12 2 3 2 Unscrew the 4 screws holding the fan motor and detach it Drain motor 1 First detach the upper and inner casing 12 2 1 and the fan 12 2 3 2 From the fan motor side undo the 2 hexagon bolts and detach the drain motor...

Page 59: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 59 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 60: ...60 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 61: ...61 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 62: ...62 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 63: ... SEG20 SEG19 SEG18 SEG17 SEG16 SEG15 COM0 COM1 COM2 COM3 SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 COM3 COM2 COM1 COM0 SEG10 Liquid Crystal Display R4 100K R5 100K R6 100K X1 3 52MHz EF0EC3524M4W R3 330K X2 32 768kHz C002RX C5 0 1 RESET terminal J3 0 J2 0 SW2 13 14 15 16 9 10 11 12 5 6 7 8 1 2 3 4 Q1 2SD1328STX R2 1K D1 SID303 R7 47 BATTERY R1 2 2 C2 4V 100 C1 4V 100 J A J B SW2 OFF Door is ope...

Page 64: ...TH1 4 3 2 1 AIR TEMP SENSOR 15K 3950 PIPE TEMP SENSOR 20K 3950 5V 6 7 5 R59 10K D4 A541SS355T R60 10K 3 C34 1000P MB C33 50V 1 NHG 5V R63 220 R61 22 1K 1 R62 11 0K 1 5V 8 4 C35 1000P MB 5V R64 25 5K 1 C36 1000P MB C32 50V 10 NHG R67 5 49K 1 5V R66 49 9K 1 C39 50V 10 NHG PH4 R72 5 90K 1 C38 50V 10 NHG R71 15 0K 1 R65 18 2K 1 5V C37 50V 1 NHG D5 A541SS355T R70 5 11K 1 R69 5 11K 1 IC4 C0BBBZ00006 C41...

Page 65: ...me count Anti dew formation control Anti freezing control 0 0 0 18 sec 3 min 30 min 20 min 6 min IC1 Microprocessor A52D4956G123 Pin No Port No Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 TO2 TO6 RXD T...

Page 66: ...B1P ME12CB1P ME14CB1P 15 1 1 Exploded View Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts 66 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 67: ... 24 DISCHARGE GRILE COMPLETE 1 CWE20C2232 25 LOUVER 1 CWE24423 26 VERTICAL LOUVER 1 CWE24C101 27 DECORATION PANEL 1 CWE35243 28 INDICATION PLATE 1 CWE39280 31 INSULATION SHEET 2 CWG10467 34 CROSS FLOW FAN COMPLETE 1 CWH02K117X 35 CONTROL BOARD BOX 1 CWH10931 36 CONTROL COVER 1 1 CWH131172 37 CONTROL COVER 2 1 CWH13424 38 CONTROL COVER 3 1 CWH13426 40 HOLDER SENSOR 1 CWH32137 43 DRAIN TRAY 1 CWH40C...

Page 68: ...Exploded View Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts 68 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P ...

Page 69: ...SHEET 1 1 CWG07165 43 INSULATION SHEET 2 1 CWG07166 44 INSULATION SHEET 3 1 CWG07167 45 CROSS FLOW FAN COMPLETE 1 CWH01C005 47 CONTROL BOARD BOX 1 CWH10527 48 CONTROL COVER 1 CWH131144 49 HOLDER LEAD WIRE 2 2 CWH31062 50 HOLDER LEAD WIRE 3 2 CWH31030 51 HOLDER LEAD WIRE 4 2 CWH31044 53 DRAIN TRAY 1 CWH40C061 54 BELT 1 CWH4605008 55 BUSHING 1 2 CWH4610440 56 CAP 1 1 CWH52061 59 BUSHING 2 1 CWH50147...

Reviews: