Panasonic CS-KN9XKD-3 Operating Instructions Manual Download Page 11

11

English

Safety Precautions

e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over 

fi

 ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been 

fi

 lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant. To avoid 

fi

 re or 

explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains 

fl

 ammable 

refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of 

fl

 ammable 

refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that 

fl

 ammable refrigerant does not 

remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

Summary of Contents for CS-KN9XKD-3

Page 1: ...erating Instructions Air Conditioner Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit nanoe G AVS ACXF55 31180 ...

Page 2: ...of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or 24 hour 2 Press SET to confirm AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL SLEEP AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING FAN SPEED QUIET POWERFUL SLEEP...

Page 3: ...s only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the operation POWER When the unit is ON disappears from the remote control display 3 Press TEMP UP TEMP DOWN to select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press for a...

Page 4: ...install the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit met...

Page 5: ... Do not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoi...

Page 6: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and ce...

Page 7: ...llow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size wit...

Page 8: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations u...

Page 9: ...erant in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 6 Detection of flammable refrigerants Under no circumstances shall potential sources of i...

Page 10: ... minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extreme care shall be taken not to over fill the refrigerating system Prior to recharging the system it shall be ...

Page 11: ...ders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are...

Page 12: ...L exit setting nanoe G AVS Indicators POWER TIMER AVS nanoe G Lateral direction FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically according to the operation mode QUIET This operation reduces airflow noise FAN SPEED QUIET nanoe G starts automatically when the unit is turned on with OFF ON OFF ON This operation can be turned ON or OFF manually by pressing This operation can...

Page 13: ...on until the sleep timer reaches 0 0h To maximise comfort while sleeping SLEEP Note SLEEP POWERFUL FAN SPEED QUIET POWERFUL Can be selected at the same time Can be activated in all modes Cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 Select TIMER ON or TIMER OFF Example OFF at 22 00 OFF 2 Set the time 3 Confirm the setting SET To cancel the timer press ...

Page 14: ...rizontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Automatic Voltage Switcher AVS When power supply is unstable where the AC voltage supplied is below 185 V or above 260 V AVS will switch off the outdoor unit to protect the compressor During this condit...

Page 15: ...filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Remove from the unit Insert into the unit To Learn More Cleaning the Air Conditioner Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an autho...

Page 16: ...ensation occurs on cold pipes and the condensed water may drip from the outdoor unit Discoloration of some plastic parts Discoloration is subjected to the types of materials used in plastic parts It is accelerated when exposed to heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due ...

Page 17: ...minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units will be not used for an extended period Activate nanoeTM G operation for 2 3 hours as an alternative to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug the unit Remove the batteries from th...

Page 18: ...ed in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbo...

Page 19: ...19 English Memo Information ...

Page 20: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 31180 SZ0621 0 ...

Reviews: