8
3 Features
•
Product
- Four modes of operation selection
- Powerful mode to reach the desired room temperature
quickly with full power and a strong airflow
- Quiet mode to provide a quiet environment by reducing
the indoor unit operating airflow sound
- 24-hour ON Timer and OFF Timer setting
- Air swing manual and automatic adjusted by Remote
Control for vertical airflow and the horizontal airflow
direction louvers can be adjusted manually by hand
- Super Alleru-Buster Filter prevent the growth of bacteria,
viruses trapped, trap dust, tobacco smoke and tiny
particles.
- Long installation piping up to 15 meter.
•
Operation Condition
- Use this air conditioner under the following temperature
range.
*DBT: Dry bulb temperature
*WBT: Wet bulb temperature
- This unit is still able to operate as a cooler with outdoor
temperature as low as -15
q
C in a non-living room, such
as a computer room, with a room temperature of 16
q
C or
above, and room humidity up to 80%.
- During cooling operation, when the outdoor temperature
drops below -15
q
C, compressor will be cut off and
resume operation again once the temperature rises more
than -15
q
C.
•
Serviceability Improvement
- Removable and washable Front Panel
- Breakdown Self Diagnosis function
•
Environmental Protection
- Non-ozone depletion substances refrigerant (R410A)
•
Operation Improvement
- Random auto restart control after power failure for safety
restart operation
- Advanced inverter technology provides outstanding
energy efficiency and powerful, flexible, comfortable
operation
Temperature (
q
C)
Indoor
Outdoor
*DBT
*WBT
*DBT
*WBT
COOLING
Maximum
32
23
43
26
Minimum
16
11
-15
-
HEATING
Maximum
30
-
24
18
Minimum
16
-
-10
-
Summary of Contents for CS-E9HKEA
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 19: ...19 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Panel ...
Page 20: ...20 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 39: ...39 ...
Page 40: ...40 15 2 Indoor Cross Flow Fan and Fan Motor ...
Page 41: ...41 ...
Page 43: ...43 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS E9HKEA CU E9HKEA ...
Page 44: ...44 ...
Page 45: ...45 ...
Page 46: ...46 ...
Page 47: ...47 16 1 2 CS E12HKEA CU E12HKEA ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 50: ...50 ...