Panasonic CS-E9BKP Supplemental Service Manual Download Page 5

New

Piping size Common

Length

(m)

Max.

Elevation

(m)

Max.

Piping

Length

(m)

Additional

Refrigerant

(g/m)

Model

Gas Liquid

E9BK

3/8”

1/4”

7.5

5

15

10

2.2.4. Low Pressure Control (Gas Leakage Detection) (Page: 29)

Conditions

E9BKP

E12BKP

Cooling/Soft Dry

Heating

Cooling/Soft Dry

Heating

1. Compressor frequency (Hz)

47

56

67

68.5

Note: Conditions 1 and 2 needed to be happened continuously for 5 minutes.

2.2.5. Low Operation Frequency Protection Control (Page: 30)

Temperature, T, for:

Cooling/Soft Dry

Heating

Indoor intake air (°C)

T < 15 or T

30

Outdoor air (°C)

T < 16 or T

38

T < 4 or T

24

2.2.6. Anti-Fog Discharge Control (Page: 32)

Operation time, T (min)

E9BKP

E12BKP

0 < T

30

Max 33 Hz

Max 44 Hz

30 < T

90

Max 26 Hz

Max 36 Hz

90 < T

420

Max 26 Hz

Max 36 Hz

2.2.7. Intake Air Temperature Control (Page: 33)

 1. When the intake air temperature is 10°C or above and remote controller setting fan speed is Lo or lower.

2.2.8. 

Auto Clean Deice Control (Page: 34)

3 Installation Instructions (Page: 54)

5

CS-E9BKP CU-E9BKP5 / CS-E12BKP CU-E12BKP5

Summary of Contents for CS-E9BKP

Page 1: ...KP CU E9BKP5 CS E12BKP CU E12BKP5 3 Installation Instructions Page 54 5 4 Electronic Circuit Diagram Page 77 82 6 Room Air Conditioner Subject Correction Of Operations Details and Electronic Circuit Diagram Please file and use this supplement manual together with the service manual for Model No CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 Order No MAC0112083C2 CONTENTS Page Page Order No MAC0202001S2 ...

Page 2: ...ift C Table d Fan Speed Shifting Mode Fan Speed Temperature Shift C Table e Start Up Shifting Mode within 60 Minutes from Start up Temperature Shift C Table f Soft Dry Mode Shifting Mode Temperature Shift C 1 Product Specifications Page 9 Unit CS E9BKP CU E9BKP5 Refrigerant R410A g oz 840 29 7 2 Operation Details 2 1 BASIC FUNCTION 2 1 1 Internal Setting Temperature Page 16 17 2 CS E9BKP CU E9BKP5...

Page 3: ...erful Mode ON 7 15 7 16 a c Soft Dry Mode 4 7 4 8 Heating Mode 1 30 1 30 b if remote controller set 18 C fan speed Hi 10 30 10 30 b d if remote control set 18 C fan speed Me Me Me Auto 9 30 9 30 b d if remote controller set 18 C fan speed Lo 8 30 8 30 b d if Powerful Mode ON 10 30 10 30 b d a If frequency decreases from MAX the following frequency performed will be depending to outdoor temperature...

Page 4: ...operate as previous operation condition 2 2 2 Total Running Current Control Page 28 1 When the total outdoor unit running current AC exceeds X value the frequency instructed for compressor operation will be decreased a step to smaller frequency number 2 If the running current does not exceed X value for five seconds the frequency instructed will be increased a step at one time to bigger frequency ...

Page 5: ...w Operation Frequency Protection Control Page 30 Temperature T for Cooling Soft Dry Heating Indoor intake air C T 15 or T 30 Outdoor air C T 16 or T 38 T 4 or T 24 2 2 6 Anti Fog Discharge Control Page 32 Operation time T min E9BKP E12BKP 0 T 30 Max 33 Hz Max 44 Hz 30 T 90 Max 26 Hz Max 36 Hz 90 T 420 Max 26 Hz Max 36 Hz 2 2 7 Intake Air Temperature Control Page 33 1 When the intake air temperatur...

Page 6: ...4 Electronic Circuit Diagram Page 77 82 6 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 ...

Page 7: ...7 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 ...

Page 8: ...8 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 ...

Page 9: ...9 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 ...

Page 10: ...10 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 ...

Page 11: ...11 CS E9BKP CU E9BKP5 CS E12BKP CU E12BKP5 MACC Printed in Malaysia ...

Reviews: