57
15.2.1.5
Error Code Table
Diagnosis
Display
Abnormality / Protection control
Abnormality
Judgment
Emergency
operation
Primary location to verify
Note
H11
Indoor/Outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan
operation only
(single type only)
•
Internal/external cable connections
•
Indoor/outdoor PCB
H12
Indoor unit capacity unmatched
-
-
•
Indoor unit total capacity
Multi only
H14
Intake air temperature unmatched
-
-
•
Intake air temperature sensor
(defective or disconnected)
H16 Outdoor
Current
Transformer
-
-
•
Decreased amount of refrigerant
•
Outdoor PCB
H19
Indoor fan motor mechanism lock
-
-
•
Fan motor
•
Indoor PCB
H23
Indoor heat exchanger temperature
sensor
Continue for 5 sec
-
•
Heat exchanger temperature sensor
(defective or disconnected)
H27
Outdoor air temperature sensor
Continue for 5 sec
○
(Single type only)
•
Outdoor air temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor 1
Continue for 5 sec
○
(Single type only)
•
Outdoor heat exchanger temperature
sensor (defective or disconnected)
H30
Outdoor discharge pipe temperature
sensor
Continue for 5 sec
-
•
Outdoor discharge pipe temperature
sensor (defective or disconnected)
H32
Outdoor heat exchanger temperature
sensor 2 (discharge pipe temp)
Continue for 5 sec
-
•
Outdoor heat exchanger temperature
sensor (defective or disconnected)
Multi only
H34
Outdoor heatsink temperature sensor
at Control Board
Continue for 2 sec
-
•
Outdoor heatsink temperature sensor
at control board (defective or
disconnected)
Multi only
H36
Outdoor gas pipe temperature sensor
Continue for 2 sec
-
•
Outdoor gas pipe temperature sensor
(defective or disconnected)
Multi only
H37
Outdoor liquid pipe temperature
sensor
Continue for 2 sec
-
•
Outdoor liquid pipe temperature
sensor (defective or disconnected)
Multi only
H39
Abnormal indoor operating unit or
standby units
- -
•
Piping connection error
•
Indoor/outdoor connection cable
connection error
Multi only
H41
Abnormal wiring or piping connection
-
-
•
Wiring or piping connection
CU-
2E15GBE
H97
Outdoor fan motor mechanism lock
-
-
•
Outdoor Fan Motor
H98
Indoor high pressure protection
-
-
•
Air filter dirty
•
Air circulation short circuit
H99
Indoor heat exchanger freeze
prevention
- -
•
Insufficient refrigerant
•
Air filter dirty
F11
Cooling/heating cycle changeover
abnormality
4 times occurrences
within 30 minutes
-
•
4-way valve
•
V-coil
F17
Indoor standby unit freezing
-
-
•
Outdoor expansion valve leakage
•
Indoor unit pipe temperature sensor
F90
PFC circuit protection
-
-
•
Outdoor PCB
•
Outdoor fan motor
F91
Refrigerant cycle abnormality
2 times occurrences
within 20 minutes
-
•
No refrigerant (3-way valve is closed)
F93
Outdoor compressor abnormal
revolution
4 times occurrences
within 20 minutes
-
•
Compressor
F95
Cooling high pressure protection
4 times occurrences
within 20 minutes
-
•
Outdoor refrigerant cycle
F96
IPM (power transistor) overheating
protection
- -
•
Express refrigerant
•
Improper heat radiation
•
Outdoor PCB
F97
Outdoor compressor overheating
protection
4 times occurrences
within 10 minutes
-
•
Insufficient refrigerant
•
Compressor
F98
Total running current protection
3 times occurrences
within 20 minutes
-
•
Excess refrigerant
•
Improper heat radiation
F99
Outdoor Direct Current (DC) peak
detection
7 times occurrences
-
•
Outdoor PCB
•
Compressor
Note:
“
○
” – Frequency measured and fan speed fixed.