10.2.7. Compressor Protection Control (Refrigeration Cycle Abnormality)
In cooling and Dry operations
1. When compressor is operated continuously for 5 minutes in the maximum cooling power: a running current of 0.7 - 1.4A and
“[Indoor intake air temperature] - [Indoor heat exchanger temperature]” < 4°C, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer LED is to be blinking. (“F91” is to be confirmed.)
In Heating operation
1. When compressor is operated continuously for 5 minutes in the rated heating power: a running current of 0.7 - 1.4A and “[Indoor
heat exchanger temperature] - [Indoor intake air temperature]” < 5°C, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer LED is to be blinking. (“F91” is to be confirmed.)
10.2.8. Four-way Valve Operation Detection Control (Switching Abnormality between
Cooling and Heating)
In Cooling operation
1. When indoor heat exchanger temperature exceeds 45°C in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer LED is to be blinking. (“F11” is to be confirmed.)
In Heating operation
1. When indoor heat exchanger temperature is below 0°C in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer LED is to be blinking. (“F11” is to be confirmed.)
10.2.9. Freeze Prevention Control (Cooling and Dry operations)
Limit of Cooling power
1. When temperature of indoor heat exchanger is below 5°C, operating frequency will be decreased.
2. When temperature of indoor heat exchanger exceeds 7°C, operating frequency will be increased. (But, up to programmed
frequency.)
3. When temperature of indoor heat exchanger is below 0°C continuously for 6 minutes, compressor will be stopped.
4. Timer LED is not blinking. (“F99” is memorized, then.)
Limit of Indoor fan speed
•
When temperature of indoor heat exchanger is below 6°C (2°C at Dry) continuously for 6 minutes, indoor fan speed will be
increased by 50 rpm.
10.2.10. Outdoor Air Temperature Control
In Cooling and Dry operations
1. When outdoor air temperature is below 25°C, the maximum power will be limited up to about 80 - 100% of the rated power.
2. When outdoor air temperature is below 18°C, the maximum power will be limited up to about 50 - 100% of the rated power.
3. When outdoor air temperature is below 11°C, the maximum power will be limited up to about 26 - 81% of the rated power.
10.2.11. Indoor Intake Air Temperature Control (Heating operation)
1. When indoor air temperature is 35°C or more, the maximum power will be limited up to the rated power.
2. When fan speed is set at “Lo” and intake air temperature is below 21°C, the maximum power will be limited up to the rated
power.
32
CS-E18EKK CU-E18EKK / CS-E21EKK CU-E21EKK
Summary of Contents for CS-E18EKK
Page 10: ...4 Dimension 4 1 Indoor Unit Remote Control 10 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 11: ...4 2 Outdoor Unit 11 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 13: ...6 Block Diagram 13 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 14: ...7 Wiring Diagram 7 1 CS E18EKK CS E21EKK 14 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 15: ...7 2 CU E18EKK CU E21EKK 15 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 16: ...8 1 Indoor Unit 8 Printed Circuit Board 16 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 17: ...8 2 Outdoor Unit 17 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 39: ...39 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 40: ...40 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 41: ...13 2 Indoor Cross Flow Fan and Fan Motor 41 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 42: ...13 3 Outdoor Propeller Fan and Fan Motor 42 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 43: ...43 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 45: ...45 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 47: ...47 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 49: ...49 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 51: ...51 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 53: ...53 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 55: ...55 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...
Page 57: ...57 CS E18EKK CU E18EKK CS E21EKK CU E21EKK ...