35
11.2 Outdoor Unit
11.2.1 Select the Best Location
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Example: For E12***
If the unit is installed at 32.8 ft (10 m) distance, the
quantity of additional refrigerant should be 1.64 oz
(50 g) .... (32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz.
((10 - 7.5) m x 20 g/m = 50 g).
11.2.1.1 Indoor/Outdoor
Installation
Diagram
11.2.2 Install the Outdoor Unit
After selecting the best location, start installation
according to Indoor/Outdoor Unit Installation
Diagram.
1 Fix the unit on concrete or rigid frame firmly
and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong
wind and earthquake.
Please fasten the installation stand firmly with
bolt or nails.
Model A B C D
E12***
22-7/16"
(570 mm)
4-1/8"
(105 mm)
23/32"
(18.5 mm)
12-19/32"
(320 mm)
E18***
24-1/8"
(613 mm)
5-5/32"
(131 mm)
5/8"
(16 mm)
14-3/16"
(360.5 mm)
Model
Capacity
(Btu/h)
Piping size
Std.
Length
Max.
Elevation
Min.
Piping
Length
Max.
Piping
Length
Additional
Refrigerant
Piping
Length for
add. gas
Gas
Liquid
E12*** 11900
1/2"
(12.7mm)
1/4"
(6.35mm)
24.6 ft
(7.5 m)
49.2 ft
(15 m)
9.8 ft
(3 m)
65.6 ft
(20 m)
0.2 oz/ft
(20 g/m)
24.6 ft
(7.5 m)
E18*** 17500
49.2 ft
(15 m)
9.8 ft
(3 m)
100 ft
(30.5 m)
0.3 oz/ft
(25 g/m)
32.8 ft
(10 m)
Installation parts you
should purchase ( )
Sleeve ( )
Bend the pipe as
closely on the wall as
possible, but be careful
that it doesn’t break.
Putty (Gum Type Sealer) ( )
Bushing-Sleeve ( )
Vinyl tape (Wide) ( )
• Apply after carrying
out a drainage test.
Additional drain
hose ( )
1/4" Liquid side
piping ( )
Gas side piping ( )
Connection cable ( )
Saddle ( )
Power supply cable ( )
11
13
/
16
"
(3
00
m
m
)
or
m
ore
3
1
5
/
1
6
"
(1
00
m
m
)
or
m
or
e
3
15
/
16
"
(10
0 m
m)
or
mo
re
39
3
/
8
"
(1
00
0
m
m
)
or
m
or
e
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult
authorized dealer/
specialist.
•
This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
a
Indoor unit
b
Outdoor
unit
Remote control holder
Remote control holder fixing screws
Remote
control
Attaching the remote control holder to the wall
8f
t
(2
.4
m
)
or
m
o
re
Floor or Grade level
A
B
C
D