82
14 Protection Control
14.1. Protection Control For All Operations
14.1.1.
Restart Control (Time Delay Safety Control)
• The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by
pressing OFF/ON button at remote control within this period.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
14.1.2.
30 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON button at the remote control
is permitted or the Auto OFF/ON button at indoor unit.
• The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
14.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
14.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1.When the IPM temperature rises to 120°C (E7~15LK) and 110°C (E18~21LK), compressor operation will stop immediately.
2.Compressor operation restarts after 3 minutes the temperature decreases to 110°C (E7~15LK) and 95°C (E18~21LK).
3.If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 18.5 A (E7 ~ 15LK) and 30.0 ± 5.0A (E18 ~ 21LK), the compressor will
stop operate. Then, operation will restart after 3 minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 2
minutes.
3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after 1 minute. If
this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer LED will be blinking (“F99”
is indicated).
Model
E7LK
E9LK
E12LK
E15LKE
E18LK
E21LK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
3.95
15.0
4.54
15.0
6.86
15.0
9.0
15.0
10.7
15.0
11.0
15.0
Cooling/Soft Dry (B)
3.6
15.0
4.12
15.0
6.35
15.0
8.5
15.0
7.7
15.0
9.6
15.0
Heating
4.37
15.0
5.57
15.0
8.03
15.0
9.8
15.0
10.7
15.0
11.5
15.0
Summary of Contents for CS-E12LKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit ...
Page 31: ...31 5 1 2 CS E18LK CS E21LK CS XE18LK CS XE21LK ...
Page 33: ...33 6 Refrigeration Cycle Diagram 6 1 CU E7LKE CU E9LKE CU E12LKE CU E15LKE ...
Page 34: ...34 6 2 CU E7LKE 3 CU E9LKE 3 CU E12LKE 3 ...
Page 35: ...35 6 3 CU E18LKE CU E21LKE ...
Page 36: ...36 7 Block Diagram 7 1 CU E7LKE CU E9LKE CU E15LKE ...
Page 37: ...37 7 2 CU E12LKE ...
Page 38: ...38 7 3 CU E7LKE 3 CU E9LKE 3 CU E12LKE 3 ...
Page 39: ...39 7 4 CU E18LKE CU E21LKE ...
Page 41: ...41 8 1 2 CS E18LK CS E21LK CS XE18LK CS XE21LK ...
Page 42: ...42 8 2 Outdoor Unit 8 2 1 CU E7LKE CU E9LKE CU E15LKE ...
Page 43: ...43 8 2 2 CU E12LKE ...
Page 44: ...44 8 2 3 CU E7LKE 3 CU E9LKE 3 CU E12LKE 3 ...
Page 45: ...45 8 2 4 CU E18LKE CU E21LKE ...
Page 47: ...47 9 1 2 CS E18LK CS E21LK CS XE18LK CS XE21LK ...
Page 48: ...48 9 2 Outdoor Unit 9 2 1 CU E7LKE CU E9LKE CU E15LKE ...
Page 49: ...49 9 2 2 CU E12LKE ...
Page 50: ...50 9 2 3 CU E7LKE 3 CU E9LKE 3 CU E12LKE 3 ...
Page 51: ...51 9 2 4 CU E18LKE CU E21LKE ...
Page 52: ...52 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 53: ...53 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 56: ...56 ...
Page 57: ...57 10 2 2 CU E18LKE CU E21LKE ...
Page 125: ...125 17 1 1 3 To remove power electronic controller 17 1 1 4 To remove discharge grille ...
Page 126: ...126 17 1 1 5 To remove control board 17 1 1 6 To remove cross flow fan and indoor fan motor ...
Page 127: ...127 ...
Page 129: ...129 17 2 1 3 To remove power electronic controller ...
Page 130: ...130 17 2 1 4 To remove discharge grille 17 2 1 5 To remove control board ...
Page 131: ...131 17 2 1 6 To remove cross flow fan and indoor fan motor ...
Page 132: ...132 ...
Page 135: ...135 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7LKE ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 ...
Page 139: ...139 18 1 2 CU E9LKE ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 ...
Page 143: ...143 18 1 3 CU E12LKE ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 ...
Page 147: ...147 18 1 4 CU E15LKE ...
Page 148: ...148 ...
Page 149: ...149 ...
Page 150: ...150 ...
Page 151: ...151 18 1 5 CU E7LKE 3 ...
Page 152: ...152 ...
Page 153: ...153 ...
Page 154: ...154 ...
Page 155: ...155 18 1 6 CU E9LKE 3 ...
Page 156: ...156 ...
Page 157: ...157 ...
Page 158: ...158 ...
Page 159: ...159 18 1 7 CU E12LKE 3 ...
Page 160: ...160 ...
Page 161: ...161 ...
Page 162: ...162 ...
Page 163: ...163 18 1 8 CU E18LKE Cooling Characteristic at Different Outdoor Air Temperature ...
Page 164: ...164 Cooling Characteristic at Different Piping Length ...
Page 165: ...165 Heating Characteristic at Different Outdoor Air Temperature ...
Page 166: ...166 Heating Characteristic at Different Piping Length ...
Page 167: ...167 18 1 9 CU E21LKE Cooling Characteristic at Different Outdoor Air Temperature ...
Page 168: ...168 Cooling Characteristic at Different Piping Length ...
Page 169: ...169 Heating Characteristic at Different Outdoor Air Temperature ...
Page 170: ...170 Heating Characteristic at Different Piping Length ...