11 Installation Instruction
11.1. Select The Best Location
INDOOR UNIT
• Do not install the unit in excessive oil fume area such as
kitchen, workshop and etc.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Example: For E9HKEA
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 50g...... (10 - 7.5) m x 20 g/m = 50 g
11.2. Indoor/Outdoor Unit
Installation Diagram
Piping size
Rated
Length
(m)
Max.
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas Liquid
E9HKEA 3/8”
1/4”
7.5
5
3
15
20
E12HKEA 1/2”
1/4”
7.5
5
3
15
20
Summary of Contents for CS-E12HKEA
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 19: ...19 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Panel ...
Page 20: ...20 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 39: ...39 ...
Page 40: ...40 15 2 Indoor Cross Flow Fan and Fan Motor ...
Page 41: ...41 ...
Page 43: ...43 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS E9HKEA CU E9HKEA ...
Page 44: ...44 ...
Page 45: ...45 ...
Page 46: ...46 ...
Page 47: ...47 16 1 2 CS E12HKEA CU E12HKEA ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 50: ...50 ...