17.5.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Refrigerant
shortage
(refrigerant leakage)
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting
When abnormality indication starts again
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
Provide sufficient air passage
Clean the air filter
Clean the indoor unit heat exchanger
Open the 2/3 way valve.
Replace the indoor unit fan motor and/or
indoor unit PCB.
Reclaim and recharge with correct amount of
refrigerant.
Replace the indoor pipe temperature sensor
Replace the indoor unit PCB
Check the air passage
Is there any short circuit?
Check the indoor unit air filter
Is the air filter dirty?
Check the dust accumulation on the indoor unit heat
exchanger
Check for gas leakage. Is Oil oozing out from the 2/3 way
valve?
Is the indoor unit heat exchanger dirty?
Check if 2/3 way valve is closed?
Check if indoor fan motor operates normally?
Check if expansion valve or strainer clogged (ice formed)?
Check the indoor pipe temperature sensor
Does it conform to the sensor characteristic chart?
Repair the pipe flare or union nuts
Reclaim and recharge refrigerant
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Caution