– 13 –
MAC9512086C2
CS-A181KE
Operation Details
1) Cooling Mode Operation
Cooling in operation according to Remote Control setting.
• When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3
minutes when the Power Switch, Remote Control is turned ON or the power supply is resumed.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3
minutes.
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the
compressor ON temperature.
Time Delay Safety Control (3 minutes)
7 minutes Time Saved Control
Anti-Freezing Control
• If the temperature of the indoor heat exchanger
falls continously below 2°C for 4 minutes, the
compressor turns off to protect the indoor heat
exchanger from freezing. The fan speed setting
remains the same.
• Compressor recommences when the indoor heat
exchanger temperature rises to 10°C (Recovery).
*
3 minutes waiting of Time Delay Safety Control
is valid for Cooling Operation.
Recovery
4 min
Compressor OFF
Indoor Heat
Exchanger
Temperature
(
°
C)
2
10
Untitled-9
6/21/00, 10:18 AM
13