Compressor Protection Control
Anti-Dew Formation Control
Automatic Fan Speed Mode
•
After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
•
If the above phenomenon is repeated for 3 times, the compressor will stop totally.
•
The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
•
Purpose is to prevent dew formation on indoor unit air discharge area.
•
When the following conditions occur for 30 minutes continuously, anti-dew formation is controlled by indoor fan speed shift to
low (CLo to HLo):
−
Indoor intake air temperature is more than 24°C and less than 30°C.
−
Remote Control setting temperature is less than 25°C.
−
Compressor is on.
−
Cooling operation mode.
−
Indoor Fan motor operate at Low fan speed.
•
This control is cancelled immediately when above condition is changed.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
•
Fan speed rotates in the range of Hi to Me.
•
Deodorizing Control.