Item
Unit
Outdoor Unit
Additional Gas Amount
g/m (oz/ft)
50 (0.5)
Refrigeration Charge Less
m (ft)
10 (32.8)
Type
Hermetic
Motor
Motor Type
Brushless (4-poles)
Compressor
Rated Output
kW
3.00
Type
Propeller
Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
-
Output Power
W
60
Fan
Fan Speed
rpm
Cooling: 550 (Top), 590 (Bottom)
Heating: 490 (Top), 530 (Bottom)
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 51 × 18
Heat Exchanger
Size (W × H × L)
mm
903.7 × 1295.4 × 38.1
ø Single
V 230
Power Source (Phase, Voltage, Cycle)
Hz 50
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Input Power
kW
Cooling: 2.21
Heating: 1.86
Heating: 2.51
Maximum Input Power For Heatpump System
kW
6.27
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 29.0 / 6.27k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 26.0 / 6.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
- / - / -
Starting Current
A
10.2
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Running Current
A
Cooling: 10.4
Heating: 8.8
Heating: 11.8
Maximum Current For Heatpump System
A
29.0
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 92
Heating: 92
Number of core
-
Power Cord
Length m
(ft)
-
Thermostat
Electronic
Control
Protection Device
Electronic Control