5.2 Disconnection Detection
Digital conversion values corresponding to the analog input are stored.
■
Applicable model
Model
Channel
AFPXHEAD4
CH0 to CH3
AFPXHEAD8
CH0 to CH7
AFPXHEA21
CH0 to CH1
■
Disconnection detection
● The disconnection detection is valid only when the analog input range setting is set to +4 to
+20 mA or +1 to +5 V.
● If a disconnection state is detected, H8000 (K-32768) is stored in the "Analog input value"
area.
● The detection level for disconnection detection is as follows.
Input range
Detection level
For +1 to +5 V
0.7 V or less
For +4 to +20 mA
2.8 mA or less