![Panasonic 6367 Specification Sheet Download Page 2](http://html.mh-extra.com/html/panasonic/6367/6367_specification-sheet_278197002.webp)
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW00435 2004-02-05
2
/
2006-08-31
Type numbers
6367
Duct detector chamber (
NOTE!
Detector & base have to be ordered
separately).
6371-06
Venturi pipe 0.6 m (Incl. end plug.)
6371-15
Venturi pipe 1.5 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)
6371-28
Venturi pipe 2.8 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)
6372 Bracket
6373
Booster fan (ext. 24 V AC, 50 mA required)
6374 Filter
Left:
How to suit the pipe to different widths of the ventilation duct.
Right:
The Bracket 6372.
Attached with each Duct detector chamber are detailed mounting and installation instructions.
Technical data
Duct air flow velocity (m/s)
0.2 to 15
Ambient temperature (
°
C)
operating
storage
-10 to +50
-25 to +75
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating
IP54
Size L x W x H (mm)
287 x 150 x 110 (the housing only)
Weight (g)
680 (the housing only)
Construction / Colour
ABS / Grey (RAL7035)
Compression glands
M16x1.5 for cable Ø=3-10 mm
Approvals
CE; EN 54
See also Product Leaflets / Technical data for the base and the detector to be used.
6367 can be mounted vertical or
horizontal on the duct and
3 x the duct diameter before or
5 x the duct diameter after a
disturbance (i.e. a bend, a filter or
a damper.