Panasonic 6367 Specification Sheet Download Page 2

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00435 2004-02-05 

2006-08-31 

 

Type numbers 

6367 

Duct detector chamber  (

NOTE!

  Detector & base have to be ordered 

separately). 

6371-06 

Venturi pipe 0.6 m  (Incl. end plug.) 

6371-15 

Venturi pipe 1.5 m  (Incl. end plug, plastic gasket and membrane gland TET 
26-35.) 

6371-28 

Venturi pipe 2.8 m  (Incl. end plug, plastic gasket and membrane gland TET 
26-35.) 

6372 Bracket 

6373 

Booster fan   (ext. 24 V AC, 50 mA required) 

6374 Filter 

 

 

 

 

Left:

  How to suit the pipe to different widths of the ventilation duct.  

Right:

  The Bracket 6372. 

Attached with each Duct detector chamber are detailed mounting and installation instructions. 

 

 

Technical data 

Duct air flow velocity (m/s) 

0.2 to 15 

Ambient temperature (

°

C) 

  operating  

 

  storage 

 

-10 to +50 
-25 to +75 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating  

IP54 

Size L x W x H (mm) 

287 x 150 x 110 (the housing only) 

Weight (g) 

680 (the housing only) 

Construction / Colour 

ABS / Grey  (RAL7035) 

Compression glands 

M16x1.5 for cable Ø=3-10 mm 

Approvals 

CE;  EN 54 

 

See also Product Leaflets / Technical data for the base and the detector to be used. 

 

6367 can be mounted vertical or 
horizontal on the duct and 
3 x the duct diameter before or 
5 x the duct diameter after a   
disturbance (i.e. a bend, a filter or 
a damper. 