62
4 Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the
diagram below.
Tape
Connection cable
Indoor & outdoor
Connection cable
Escapement
Terminal
Board
Earth Wire
longer than
others
AC wires
for safety
reason
Outdoor unit
Indoor & outdoor
Connection cable
Holder
Recommended
length (mm)
Recommended
length (mm)
a
b
c
d
35 35 35 55
Terminals on the indoor unit
Colour of wires
Terminals on the outdoor unit
1 2 3
1 2 3
WARNING
This equipment must be properly earthed.
5 Secure the connection cable onto the control board with the holder.
o
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s
respectively.
o
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
12.2.4.1 Wire Stripping and Connecting Requirement
WARNING
RISK OF FIRE
JOINING OF WIRES
MAY CAUSE
OVERHEATING
AND FIRE.
OR
Use complete
wire without joining.
Use approved
socket and plug
with earth pin.
Wire connection
in this area must
follow to national
wiring rules.
OR
OR
Do not joint wires
Wire stripping
No loose strand
when inserted
10 ± 1 mm
5 mm or more
Indoor/outdoor connection
terminal board
(gap between wires)
Conductor
fully inserted
Conductor
over inserted
Conductor not
fully inserted
ACCEPT
PROHIBITED
PROHIBITED
12.2.5 Cutting and Flaring the Piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
1. To cut
When properly flared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the flare part comes into contact with the
connections, carefully check the flare finish.
Improper fl aring
Inclined Surface
damaged
Cracked Uneven
thickness
3. To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe