Panametrics VeriDri User Manual Download Page 11

VeriDri™ User’s Manual

3

 Making the Wiring Connections

3.

Using a 1-1/8 in. wrench, tighten the probe securely into the system using the probe hex nut.

4.

Making the Wiring Connections

You must wire the transmitter using the factory-supplied cable, which is available in a variety of lengths.

Note:

If you need to lengthen cables, refer t

Table 1

 below to splice an extension onto the existing cable. Be sure 

to connect positive to positive and negative to negative.

Use the following steps to wire the transmitter to your system:

1.

Push the female connector end on the transmitter cable into the mating male connector on the transmitter 

module. Make sure the pins are properly aligned. Then, secure the connectors together by sliding the metal 

sleeve on the cable over the connectors and turning it clockwise until it is tight.

2.

Using the flying leads at the other end of the transmitter cable, connect the transmitter to your power supply and 

data acquisition system (DAS), as shown in 

Figure 2 on page 4

. Refer to 

Table 1

 below for a description of the 

leads on the factory-supplied cable.

3.

Trim any unused leads back to the outer cable jacket, to remove the bare tinned wire and prevent accidental 

short circuits.

The VeriDri is now ready for operation.

CAUTION!

Do not apply force on the transmitter module to tighten the unit into its fitting.

Table 1: Cable Lead Descriptions

Lead Color*

Connection Description

Blue

(+) 7 to 28 VDC

Brown

 (

) 7 to 28 VDC

Shield

Connect to ground, if desired

*

The blue and brown leads also produce a current output 

equivalent to 4 to 20 mA.

Probe Hex Nut

Summary of Contents for VeriDri

Page 1: ...panametrics com 916 095 D Dec 2021 VeriDri Moisture Transmitter User s Manual...

Page 2: ......

Page 3: ...al contains one or more registered trademarks of Baker Hughes Company and its subsidiaries in one or more countries All third party product and company names are trademarks of their respective holders...

Page 4: ...ii no content intended for this page...

Page 5: ...to the auxiliary equipment Examples include safety glasses protective headgear safety shoes etc Unauthorized Operation Make sure that unauthorized personnel cannot gain access to the operation of the...

Page 6: ...vironment In order to avoid the dissemination of those substances in our environment and to diminish the pressure on the natural resources we encourage you to use the appropriate take back systems Tho...

Page 7: ...onnections 3 5 Operating the Transmitter 4 5 1 Powering Up 5 5 2 Error Handling 5 6 Cleaning the Transmitter Probe 5 6 1 Removing the Transmitter 5 6 2 Soaking the Sensor and Shield 6 6 3 Evaluating t...

Page 8: ...Contents vi VeriDri User s Manual no content intended for this page...

Page 9: ...unit be installed in a sample system to protect the probe from coming into contact with damaging elements in the process Before constructing a sample system you should consult a Panametrics Applicati...

Page 10: ...om damaging elements in the process 2 The probe is mounted into the process via the 3 4 16 straight male thread located on the probe Thread the probe end of the transmitter into the process sample sys...

Page 11: ...secure the connectors together by sliding the metal sleeve on the cable over the connectors and turning it clockwise until it is tight 2 Using the flying leads at the other end of the transmitter cabl...

Page 12: ...ly or worry about losing data during a power loss Probes may need to be cleaned occasionally depending on the application Consult a Panametrics Applications Engineer for recommended cleaning intervals...

Page 13: ...latex gloves An oven set at 50 C 2 C 122 F 3 6 F for drying the probe A 1 1 8 in wrench Refer to the following sections to properly clean the probe 6 1 Removing the Transmitter Complete the following...

Page 14: ...50 C 2 C 122 F 3 6 F for 24 hours 6 3 Evaluating the Probe To evaluate the probe complete the following steps 1 Re connect the cable to the transmitter module and measure the ambient dew point Make su...

Page 15: ...erating Temperature 40 to 60 C 40 to 140 F Storage Temperature 70 C 158o F maximum Note The probe should be stored with the plastic cover and desiccant packet threaded onto the probe Store it in a coo...

Page 16: ...onics Module w cable 5 93 1 125 in 15 06 2 86 cm Weight 5 oz 140 g 7 4 Moisture Sensor Specifications Sensor Type Thin film aluminum oxide moisture sensor probe Calibration Each sensor is individually...

Page 17: ...pose and warranties arising from course of dealing or usage or trade Return Policy If a Panametrics instrument malfunctions within the warranty period the following procedure must be completed 1 Notif...

Page 18: ...Warranty 10 VeriDri User s Manual no content intended for this page...

Page 19: ...trial Locations EN 61326 2 3 2006 EN 60529 2001 IP67 following the provisions of the 2004 108 EC EMC Directive The unit listed above and any ancillary equipment supplied with it do not bear CE marking...

Page 20: ...no content intended for this page...

Page 21: ......

Page 22: ...one or more countries All third party product and company names are trademarks of their respective holders 916 095 D Customer Support Centers U S A 1100 Technology Park Drive Billerica MA 01821 4111...

Reviews: