8.2. Electrical connection
1
2
3
4
5
6
1
7
9
10
11
8
12
Switch positions as delivered:
•
HPF: off ,
•
Power: 100%
(1) Enclosure
with connection plate and slot for assembly of
mounts
(2) Sealing plate
(3) Connection plate
(4) 4 x screws for fastening the connecting
plate (3) to the enclosure
(5) Bore with blind plug
for second cable gland / 100 V link
(6) Cable gland
pre-assembled for introduction of the con-
nection cable
(7) 100 V connector of the connection plate
(8) Fuse
(9) Slide switch for power tap
stated in %: 100 / 50 / 25 / 12.5
= P 04-EN54: 75 W / 37.5 W / 18.8 W / 9.8 W
= P 08-EN54: 125 W / 62 W / 32 W / 15 W
(10)
Slide switch for high-pass fi lter
(11) Indicator
lights up green when pilot signal is detected
Frequency range: 20 kHz - 23 kHz
Required signal level (min): 6 V
rms
(12) Connection for signal input lead
suitable for cable diameters up to 2.5 mm
2
The loudspeakers from the Pan EVAC series
with an EN 54-24 option are passive 100 V
systems. An external amplifi er is required to
operate them.
These systems have identical connections
for the feed cable. The rated power can be
adjusted via an internal switch. Likewise, the
high-pass fi lter can be activated via a switch.
For connecting (linking) to other loudspeakers,
there is a second cable gland.
The cables are to be adequately sized in terms of
their diameter. The cable ends to be connected
must be fi tted with wire end ferrules.
The loudspeaker is delivered with a sealing plate
and two M16 cable glands. These are used to
seal the loudspeaker and to relieve strain on the
connection cables. The cable glands are suitable
for Ø 4.5 - 10 mm. If only one connection cable
is used, the second cable gland is to be replaced
by a plug.
NOTICE