Pan Acoustics P 08-EN 54 Manual Download Page 1

QUALITY 
MADE IN GERMANY
SINCE 2002

Pan Acoustics GmbH │ Schweigerstr. 13d │ D-38302 Wolfenbüttel │ Germany │ Tel.: +49 (0) 5331 900 95 70 │ E-mail: [email protected]

www.pan-acoustics.de

Pan Acoustics reserves the right to modify products without prior notice.

All products are designed, developed and manufactured by Pan Acoustics in Germany.

Doc. No

.: 2022_01608.V1 - 03.05.2022

DOCUMENTATION

B E A M

2-LINE

SPEAKER

E V A C

Page 1 of 16

MANUAL PAN EVAC SERIES 

EN 54-24 CERTIFIED LOUDSPEAKERS FOR VOICE ALARM SYSTEMS

Read the manual carefully before putting the device into operation.

The manual must be retained.

Shapely.

Versatile.

Functional.

Pan EVAC P 04-EN54 

Pan EVAC P 08-EN54

Summary of Contents for P 08-EN 54

Page 1: ...ithout prior notice All products are designed developed and manufactured by Pan Acoustics in Germany Doc No 2022_01608 V1 03 05 2022 DOCUMENTATION B E A M 2 LINE SPEAKER E V A C Page 1 of 16 MANUAL PAN EVAC SERIES EN 54 24 CERTIFIED LOUDSPEAKERS FOR VOICE ALARM SYSTEMS Read the manual carefully before putting the device into operation The manual must be retained Shapely Versatile Functional Pan EV...

Page 2: ...ent must be kept with the product or in a safe place so that it is available when needed If the product is resold the document must be handed over to the new owner in printed or electronic form Pan Acoustics reserves the right to change update the document without prior notice The latest version of this document can be downloaded from the Pan Acoustics website Pan Acoustics GmbH Schweigerstr 13d 3...

Page 3: ...ery 6 7 Setup location 6 8 Assembly and connection 7 8 1 Assembly 7 8 2 Electrical connection 8 9 Operating conditions 9 10 Service and repair 9 11 Maintenance measures 9 12 EC conformity 9 13 WEEE declaration disposal 10 14 Contact address 10 15 Mount 10 16 Technical data loudspeaker 11 16 1 Pan EVAC P 04 EN54 11 16 2 Pan EVAC P 08 EN54 12 17 Technical illustrations loudspeaker 13 17 1 Pan EVAC P...

Page 4: ...symbol indicates a hazard with a low level of risk Failure to observe this instruction may result in minor injuries or damage to property All information in this manual is based on the product properties available at the time of writing and the safety regulations applicable at that time This manual describes the design function and connection of the Pan EVAC EN 54 24 loudspeaker systems P 04 EN54 ...

Page 5: ...ed and secured against accidental operation if the product shows signs of visible damage contains loose parts no longer works flawlessly has been stored for a long time under unfavourable conditions e g in humid rooms was subjected to severe transport stress e g with improper packaging To avoid injuries such as hearing damage due to excessive volume levels persons should never stand directly in fro...

Page 6: ...st be secured and labelled accordingly It must also be ensured that no intentional or accidental oper ation by third parties is possible The loudspeakers can be operated in interior rooms or in outdoor areas When operating them inside rooms ensure adequate air circulation The device may be damaged by condensation It should therefore be appropriately accli matised before operation The ambient tempe...

Page 7: ...n the long term For a safe and durable connection plug and screw connections must be dimensioned according to the acting forces that may occur through lever effects In case of doubt as to the type and composition of the building structure consult a structural engineer CONNECTION OF THE LOUDSPEAKER AND MOUNT All mounts sourced via Pan Acoustics for the Pan EVAC EN 54 are delivered with suitable ins...

Page 8: ...20 kHz 23 kHz Required signal level min 6 Vrms 12 Connection for signal input lead suitable for cable diameters up to 2 5 mm2 The loudspeakers from the Pan EVAC series with an EN 54 24 option are passive 100 V systems An external amplifier is required to operate them These systems have identical connections for the feed cable The rated power can be adjusted via an internal switch Likewise the high...

Page 9: ... also not be exposed to strong vibrations 9 Operating conditions 10 Service and repair Service and repair work may only be carried out by persons and partners instructed by Pan Acoustics No service or repair measures are to be performed on the device that exceed the statements made in chapter 11 Maintenance Contact data see chapter 14 Contact address The following measures are to be carried out at...

Page 10: ...ose of the device in accordance with the applicable regulations and any contractual agreements If you have any questions about disposal please contact your dealer distributor or us 14 Contact address Pan Acoustics GmbH Schweigerstr 13d 38302 Wolfenbüttel Germany Tel 49 0 5331 900 95 70 Fax 49 0 5331 900 95 79 E mail support pan acoustics de 15 Mount The loudspeakers from the Pan EVAC series can be...

Page 11: ...96 3 dBSPL 4 m Sensitivity 1 W 4 m 81 6 dBSPL Frequency range 190 Hz 15 kHz 10 dB 6 dB HPF off Horizontal radiation pattern 500 Hz 360 1000 Hz 215 2000 Hz 145 4000 Hz 98 Vertical radiation pattern 500 Hz 160 1000 Hz 75 2000 Hz 30 4000 Hz 15 Tilt angle Vertical 4 Range 15 m MECHANICAL PROPERTIES Pilot signal detection Indicator green LED behind protective grid Frequency range 20 kHz 23 kHz Required...

Page 12: ...nsitivity 1 W 4 m 79 dBSPL Frequency range 140 Hz 15 kHz 10 dB 6 dB HPF off Horizontal radiation pattern 500 Hz 360 1000 Hz 215 2000 Hz 147 4000 Hz 100 Vertical radiation pattern 500 Hz 87 1000 Hz 37 2000 Hz 25 4000 Hz 8 Tilt angle Vertical 4 Range 20 m MECHANICAL PROPERTIES Pilot signal detection Indicator green LED behind protective grid Frequency range 20 kHz 23 kHz Required signal level min 6 ...

Page 13: ... Pan Acoustics GmbH Page 13 of 16 Manual Doc No 2022_01608 V1 03 05 2022 17 Technical illustrations loudspeaker 17 1 Pan EVAC P 04 EN54 506 mm 118 mm 18 mm 107 mm ...

Page 14: ... Pan Acoustics GmbH Page 14 of 16 Manual Doc No 2022_01608 V1 03 05 2022 17 2 Pan EVAC P 08 EN54 906 mm 118 mm 18 mm 107 mm ...

Page 15: ... Pan Acoustics GmbH Page 15 of 16 Manual Doc No 2022_01608 V1 03 05 2022 18 Certificate ...

Page 16: ...c No 2022_01608 V1 03 05 2022 CONTACT Pan Acoustics GmbH Schweigerstr 13d D 38302 Wolfenbüttel Germany Tel 49 0 5331 900 95 70 Fax 49 0 5331 900 95 79 E mail contact pan acoustics de www pan acoustics de QUALITY MADE IN GERMANY SINCE 2002 ...