12

GHI 

Type infrared ceramic heaters

 

User’s Manual

  9.picture: Installation of the GHI heaters and safety distances

Tilting angle of heater should be adjusted according to values given in referring plan. Most frequent values: 45° and 60°, which 

mean the pitch of ceramic surface to the floor. At hanging from the ceiling, at least 30° minimum tilting must be ensured! The 

minimal tilting what is allowed at GHI-23 and GHI-36 appliances is 45°!

Adjustable device holder gaps                                                           

min. 500mm

min.800mm

Suspension

Warning! DO NOT ALLOWED to install he GHI appliances into “A” and “B” specified fire-protection  

class! The installation must comply with the valid standards!

Disregard of these instructions can result in death, injury or property damage!

 

Infrared heaters are to be mounted on welded or assembled consoles built in the side wall of the hall to be heated, eventually on the 

ceiling, and secured with M8 bolts.

The heaters do not possess integral combustion product exhausting system, so must be ventilate the room. Min. 16 max. 24 m³/h air 

exchange is necessary at every built-in/kW.

Ventilation

The distance of any inflammable materials from the heater must be chosen with ensure, that the surface temperature of these materials 

could NOT reach 50 °C. In cases when it is not possible, a fireproof heat protection plate must be used.

Protective distances to be kept considering flammable materials

Warning! The installation of appliance must be only executed by qualified service or specialist author

-

ized by retailer.

The 2 years guarantee of appliance can be ensured only in this case.

 

6.

  

Appliance operation

Before putting operation of appliance the leak-proof/pressure test of gas sup-ply system must be fulfilled. Clean duct system of gas supply 

from any contamination. 

•  Check the presence and cleanness of gas filter located before the appliance

•  Check the presence and suitability of pressure regulator located centrally or before every appliance.( the pressure regulator is 

needed if the gas supply pressure is higher than 60 mbar,in this way the capacity of pressure regulator can be max. 60 mbar)

•  Make sure of protective ground of appliance. 

•  Check the proper electrical connection of temperature regulator.

•  Open the gas supply valve.

•  Check the gas pressure on the inlet side of (magnetic) solenoid valve.(the maximum allowed pressure is 60 mbar).

•  Connect the mains voltage to the appliance by temperature regulator or central stage main-switch.

•  Check the outlet pressure of solenoid valve, whether the set up pressure –nozzle pressure – is suitable for the type of gas.

Adjustment of gas pressure happens only in that case, when device does not operate satisfactorily within the value adjusted by the 

manufacturer. Device is factory-adjusted, but because of the different positioning circumstances it is practical to adjust it after the on-the-

spot installation. The characteristic heat technical data is only expected from well-adjusted devices. A qualified technician should make 

adjustment of heating device.

45°

Summary of Contents for GHI Series

Page 1: ...NATURAL OR PROPAN GAS WORKING GAS INFRARED CERAMIC HEATERS EN www pakole com 009_022_011_190415_V004_EN Appliance types GHI 7 36 User s Manual...

Page 2: ...lenoid type VK4125C 2005 S4965R2027 type 10 Electrical connection scheme of HONEYWELL S4965R2027 11 control 11 Optional accessories 11 Suspension 12 Protective distances to be kept considering flammab...

Page 3: ...ed help or information concerning the appliances for example installation guide or labels etc in that case contact with the manufacturer This appliance must not be used by children and mentally or sen...

Page 4: ...h during operation despite warming of appliance preserves its stability 2 General Instruction making up of gas and electrical connection in compliance with the specifications it is proposed to connect...

Page 5: ...TION COMPULSORY USE PROTECTIVE GLOVES If you have to disassemble the unit use special protective gloves Beware of sharp edges inside the unit Beware of roof corners of outdoor units Keep suction grids...

Page 6: ...face of the ceramics is 850 900 C This surface has a high radiant intensity and quick heat passing The construction of the equipment is not insure to lead away the being combustion product so in this...

Page 7: ...Type infrared ceramic heaters User s Manual 5 Installation Drawings and dimensions of the appliances control section Reflector mounting bracket This is not the part of the equipment mixing housing Iso...

Page 8: ...e indications of the static expert 3 Please set the right angle of the unit and fix the srews THE INSTALATION ANGEL OF THE CERAMIC HEATERS TO THE HORIZONTAL PLANE REFERED TO THE CERAMIC SURFACE CAN NO...

Page 9: ...ce or centrally namely one piece into the gas supply pipe In case of unique solution namely there is pres sure regulator before each appliance before every pressure regulator in case of centrally moun...

Page 10: ...the diagram which was attached to the appliance ELECTRICAL CONNECTING SPECIFICATIONS The electrical supply 230V 50Hz grounded Approximately 20W electrical performance per appliance The appliance must...

Page 11: ...rode check the distance to the ceramic surface and to the protective grid Furthermore if it is necessary adjust again the desired maximum 4 mm value to the ceramic Electrodes must not be closer than 1...

Page 12: ...stallation of appliance must be only executed by qualified service or specialist author ized by retailer The 2 years guarantee of appliance can be ensured only in this case 6 Appliance operation Befor...

Page 13: ...ecialist or a specialist Check at the beginning of season Maintenances The first adjustment of the appliance must be carried out only from a well educated technician To fulfil this requirement the eas...

Page 14: ...k ceramic plates Blow them sometimes through by compressed air when it is switched off and cool enough d Check if ceramic plates are broken or not by a survey There is a bright line dur ing glowing po...

Page 15: ...utomatic control Nozzle pressure is not suitable Replace the solenoid valve Replace the differential switch Check the input and output pres sure on the solenoid valve The ceramic burner ig nites but s...

Page 16: ...Capacity Stage 1 50 kW Connecting gas pressure mbar mbar NG S gas Propane GHI 7 A 6 6 20 37 50 GHI 11 A 9 9 8 2 20 37 50 GHI 18 A 16 3 13 5 20 37 50 GHI 23 B 19 7 9 85 20 37 50 GHI 36 B 29 8 14 9 20 3...

Page 17: ...2H3B P 20 30 FI II2H3B P 20 30 FR II2E 3 II2H3P 20 25 30 37 GR II2H3 II2H3P 20 30 37 37 NL I3B P I3P II2L3B P 25 30 50 IE II2H3 II2H3P 20 30 37 37 PL II2E3P II2E3B P 20 37 30 LV II2H3B P 20 30 LT II2H...

Page 18: ...t output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 69 4 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 69 4 Envelope loss factor Fenv...

Page 19: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 70 1 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 70 1 Envelope loss factor Fen...

Page 20: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 70 7 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 70 7 Envelope loss factor Fen...

Page 21: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 73 3 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 73 3 Envelope loss factor Fen...

Page 22: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 73 9 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 73 9 Envelope loss factor Fen...

Page 23: ...rized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caused mistake...

Page 24: ...PAKOLE TRADE Ipari s Kereskedelmi Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 Honlap http www pakole hu E mail mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole hu...

Reviews: