NATURAL OR PROPAN -GAS WORKING
GAS INFRARED CERAMIC HEATERS

EN

www.pakole.com

009_022_01

1_190415_V004_EN

Appliance types:

GHI-7...36

User’s Manual

Summary of Contents for GHI Series

Page 1: ...NATURAL OR PROPAN GAS WORKING GAS INFRARED CERAMIC HEATERS EN www pakole com 009_022_011_190415_V004_EN Appliance types GHI 7 36 User s Manual...

Page 2: ...lenoid type VK4125C 2005 S4965R2027 type 10 Electrical connection scheme of HONEYWELL S4965R2027 11 control 11 Optional accessories 11 Suspension 12 Protective distances to be kept considering flammab...

Page 3: ...ed help or information concerning the appliances for example installation guide or labels etc in that case contact with the manufacturer This appliance must not be used by children and mentally or sen...

Page 4: ...h during operation despite warming of appliance preserves its stability 2 General Instruction making up of gas and electrical connection in compliance with the specifications it is proposed to connect...

Page 5: ...TION COMPULSORY USE PROTECTIVE GLOVES If you have to disassemble the unit use special protective gloves Beware of sharp edges inside the unit Beware of roof corners of outdoor units Keep suction grids...

Page 6: ...face of the ceramics is 850 900 C This surface has a high radiant intensity and quick heat passing The construction of the equipment is not insure to lead away the being combustion product so in this...

Page 7: ...Type infrared ceramic heaters User s Manual 5 Installation Drawings and dimensions of the appliances control section Reflector mounting bracket This is not the part of the equipment mixing housing Iso...

Page 8: ...e indications of the static expert 3 Please set the right angle of the unit and fix the srews THE INSTALATION ANGEL OF THE CERAMIC HEATERS TO THE HORIZONTAL PLANE REFERED TO THE CERAMIC SURFACE CAN NO...

Page 9: ...ce or centrally namely one piece into the gas supply pipe In case of unique solution namely there is pres sure regulator before each appliance before every pressure regulator in case of centrally moun...

Page 10: ...the diagram which was attached to the appliance ELECTRICAL CONNECTING SPECIFICATIONS The electrical supply 230V 50Hz grounded Approximately 20W electrical performance per appliance The appliance must...

Page 11: ...rode check the distance to the ceramic surface and to the protective grid Furthermore if it is necessary adjust again the desired maximum 4 mm value to the ceramic Electrodes must not be closer than 1...

Page 12: ...stallation of appliance must be only executed by qualified service or specialist author ized by retailer The 2 years guarantee of appliance can be ensured only in this case 6 Appliance operation Befor...

Page 13: ...ecialist or a specialist Check at the beginning of season Maintenances The first adjustment of the appliance must be carried out only from a well educated technician To fulfil this requirement the eas...

Page 14: ...k ceramic plates Blow them sometimes through by compressed air when it is switched off and cool enough d Check if ceramic plates are broken or not by a survey There is a bright line dur ing glowing po...

Page 15: ...utomatic control Nozzle pressure is not suitable Replace the solenoid valve Replace the differential switch Check the input and output pres sure on the solenoid valve The ceramic burner ig nites but s...

Page 16: ...Capacity Stage 1 50 kW Connecting gas pressure mbar mbar NG S gas Propane GHI 7 A 6 6 20 37 50 GHI 11 A 9 9 8 2 20 37 50 GHI 18 A 16 3 13 5 20 37 50 GHI 23 B 19 7 9 85 20 37 50 GHI 36 B 29 8 14 9 20 3...

Page 17: ...2H3B P 20 30 FI II2H3B P 20 30 FR II2E 3 II2H3P 20 25 30 37 GR II2H3 II2H3P 20 30 37 37 NL I3B P I3P II2L3B P 25 30 50 IE II2H3 II2H3P 20 30 37 37 PL II2E3P II2E3B P 20 37 30 LV II2H3B P 20 30 LT II2H...

Page 18: ...t output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 69 4 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 69 4 Envelope loss factor Fenv...

Page 19: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 70 1 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 70 1 Envelope loss factor Fen...

Page 20: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 70 7 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 70 7 Envelope loss factor Fen...

Page 21: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 73 3 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 73 3 Envelope loss factor Fen...

Page 22: ...at output Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 73 9 Envelope insulation class U 0 0 W m2K Radiant factor at minimum heat output RFmin 73 9 Envelope loss factor Fen...

Page 23: ...rized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caused mistake...

Page 24: ...PAKOLE TRADE Ipari s Kereskedelmi Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 Honlap http www pakole hu E mail mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole hu...